A Smooth LVRT Control Strategy for Single-Phase Two-Stage Grid-Connected PV Inverters


Vol. 15, No. 3, pp. 806-818, May  2015
10.6113/JPE.2015.15.3.806


PDF     Full-Text

 Abstract

Based on the inherent relationship between dc-bus voltage and grid feeding active power, two dc-bus voltage regulators with different references are adopted for a grid-connected PV inverter operating in both normal grid voltage mode and low grid voltage mode. In the proposed scheme, an additional dc-bus voltage regulator paralleled with maximum power point tracking controller is used to guarantee the reliability of the low voltage ride-through (LVRT) of the inverter. Unlike conventional LVRT strategies, the proposed strategy does not require detecting grid voltage sag fault in terms of realizing LVRT. Moreover, the developed method does not have switching operations. The proposed technique can also enhance the stability of a power system in case of varying environmental conditions during a low grid voltage period. The operation principle of the presented LVRT control strategy is presented in detail, together with the design guidelines for the key parameters. Finally, a 3 kW prototype is built to validate the feasibility of the proposed LVRT strategy.


 Statistics
Show / Hide Statistics

Cumulative Counts from September 30th, 2019
Multiple requests among the same browser session are counted as one view. If you mouse over a chart, the values of data points will be shown.



Cite this article

[IEEE Style]

F. Xiao, L. Dong, S. F. Khahro, X. Huang, X. Liao, "A Smooth LVRT Control Strategy for Single-Phase Two-Stage Grid-Connected PV Inverters," Journal of Power Electronics, vol. 15, no. 3, pp. 806-818, 2015. DOI: 10.6113/JPE.2015.15.3.806.

[ACM Style]

Furong Xiao, Lei Dong, Shahnawaz Farhan Khahro, Xiaojiang Huang, and Xiaozhong Liao. 2015. A Smooth LVRT Control Strategy for Single-Phase Two-Stage Grid-Connected PV Inverters. Journal of Power Electronics, 15, 3, (2015), 806-818. DOI: 10.6113/JPE.2015.15.3.806.