A Fault Tolerant Control Technique for Hybrid Modular Multi-Level Converters with Fault Detection Capability


Mahmoud Abdelsalam, Mostafa Ibrahim Marei*, Hatem Yassin Diab**, and Sarath B. Tennakoon***


†,**Department of Electrical Energy Engineering, Arab Academy for Science, Technology and Maritime Transport, Smart Village, Egypt

*Electrical and Control Department, College of Engineering and Technology, Arab Academy for Science, Technology and Maritime Transport, Cairo, Egypt

***Faculty of Computing, Engineering and Sciences, Staffordshire University, Stoke on Trent, England, UK



Abstract

In addition to its modular nature, a Hybrid Modular Multilevel Converter (HMMC) assembled from half-bridge and full-bridge sub-modules, is able to block DC faults with a minimum number of switching devices, which makes it attractive for high power applications. This paper introduces a control strategy based on the Root-Least Square (RLS) algorithm to estimate the capacitor voltages instead of using direct measurements. This action eliminates the need for voltage transducers in the HMMC sub-modules and the associated communication link with the central controller. In addition to capacitor voltage balancing and suppression of circulating currents, a fault tolerant control unit (FTCU) is integrated into the proposed strategy to modify the parameters of the HMMC controller. On advantage of the proposed FTCU is that it does not need extra components. Furthermore, a fault detection unit is adapted by utilizing a hybrid estimation scheme to detect sub-module faults. The behavior of the suggested technique is assessed using PSCAD offline simulations. In addition, it is validated using a real-time digital simulator connected to a real time controller under various normal and fault conditions. The proposed strategy shows robust performance in terms of accuracy and time response since it succeeds in stabilizing the HMMC under faults.


Key words: Fault detection unit, Fault tolerant control unit, Hardware in the loop, Hybrid modular multilevel converter, Recursive least square


Manuscript received Jul. 13, 2016; accepted May 2, 2017

Recommended for publication by Associate Editor Kyeon Hur.

Corresponding Author: mahmoud.abdelsalam@research.staffs.ac.uk Tel: +20-1282404905, Arab Academy Sci., Tech. Marit. Transp.

*Electrical Contr. Dept., College of Eng. Tech., Arab Academy Sci., Tech. Marit. Transp., Egypt

**Dept. of Electr. Energy Eng., Arab Academy Sci., Tech. Marit. Transp., Egypt

***Faculty of Computing, Eng. and Sci., Staffordshire University, UK



Ⅰ. INTRODUCTION

Modular multilevel converters (MMC) have a lot of potential for use in various industrial and energy systems. They have the same advantages as two-level voltage source converters (VSC) such as independent control of active and reactive powers, and a small footprint when compared to line commutated converters (LCC). However, the MMC has some unique features that make it very suitable for use in high voltage and high current applications. These features include improved quality of the output voltage and current due to an increased number of the voltage levels without the need for filtering devices, a reduced switching frequency that is translated into lower switching losses, and elimination of the dc-link capacitor [1], [2]. The MMC is constructed from either half-bridge sub-modules (HBSM) or full-bridge sub-modules (FBSM) depending on the application it will be used in. The main advantage of the HBSM-MMC is a reduced number of switching devices, which means that the switching losses are low. However, it fails to protect the system against DC faults since the HBSM has only two quadrant operation. Therefore, it cannot reverse the current. The DC fault blocking capability can be easily achieved using a FBSM-MMC since the FBSM has a four quadrant operation. Therefore, it can stop the propagation of DC faults. However, when looking at the performance of the converter itself, the switching losses are increased since the current passes through two IGBTs instead of one. In addition, the capital cost of a FBSM-MMC is doubled when compared to the HBSM-MMC since each sub-module needs four IGBTs instead of two [3]. This has motivated researchers to innovate a new type of multi-level converter called the hybrid modular multi-level converter (HMMC), which is able to compromise a new structure that mixes the advantages of the HBSM-MMC and the FBSM- MMC [4].

To guarantee stable and accurate operation for a HMMC, the sub-module capacitors must be charged to the same voltage level. This process is called capacitor voltage balancing. Furthermore, these voltages should follow a pre- defined reference to reach a desired level of output voltage [5]-[7].

Due to the modular nature of the HMMC and the series connection of differently structured sub-modules, any sub- module fault threatens the safety of the other healthy sub- modules since a fault may propagate and cause cascading failure for the whole arm. On the other hand, it is not recommended to shut-down the whole converter to recover a sub-module from a fault. All of these challenges have directed research to the concept of fault detection and fault tolerant control that enable the HMMC to operate under the fail-to-safe principle with acceptable performance even if some of the sub-modules are subjected to faults [8], [9]. The first step to implement the fault detection algorithm is to classify the faults of the HMMC sub-modules. The sub- module is the building identity of the HMMC and it is subject to different open-circuit or short-circuit faults in the switches or capacitors, which affect the reliability of the HMMC [8], [9]. It was found that 30% of the failures in power electronic converters occur in the switches [10]. In addition, it is important to mention that the time required to identify an internal fault should be less than 5ms to be able to block the converter before the short circuit current reaches its full value. Therefore, the quick detection of switch faults is essential to enhancing the reliability of the HMMC.

A fault tolerant control system aims to outperform a faulty sub-module and to stabilizing the HMMC [11]. In the literature, most fault tolerant control systems depend on either redundant components or special circuits which add an extra cost for items that are not be used during normal operation [12].

This paper presents a controller for the capacitor voltage balancing of a HMMC based on the capacitor voltage estimation algorithm instead of direct measurements of the sub-module capacitor voltages. Moreover, the fault detection and fault tolerant control techniques, proposed for the MMC in [13], are generalized for the HMMC and integrated into the proposed control strategy. The main contribution of the proposed technique when compared to other techniques is that the indicated strategy controls the HMMC in both normal and abnormal conditions without the incorporation of any capacitor voltage measurements, extra power circuits or special power circuits while keeping perfect power quality in both conditions. As a result, the cost is significantly reduced and the reliability of the control system is increased due to the reduced number of components and the limited number of communication channels, which make the proposed strategy attractive for practical implementations of a HMMC with a large number of sub-modules. The proposed control is tested using the concept of the hardware in the loop (HIL) by connecting a real-time digital simulator to a physical controller to practically evaluate its dynamic performance. Different operation scenarios are considered to assess the performance of the proposed unified control scheme.



Ⅱ. HYBRID MODULAR MULTI-LEVEL CONVERTER MODELLING


A. The HMMC Structure and Theory of Operation

The three-phase HMMC is assembled from three legs as shown in Fig. 1. Each leg is formed from two arms where each arm includes a number of HBSMs and FBSMs connected in series. The sub-modules, which are considered to be the building blocks of the HMMC, transfer the energy between the dc and the ac sides through different operation modes as illustrated in Table I and Table II.


그림입니다.
원본 그림의 이름: image1.png
원본 그림의 크기: 가로 1049pixel, 세로 613pixel

Fig. 1. Three-phase HMMC topology and sub-module circuits.


TABLE I HBSM MODES OF OPERATION

Mode

I

II

S1

Switched on

Switched off

S2

Switched off

Switched on

Description

The output voltage from the sub-module has a positive polarity. The capacitor is charging or discharging, depending on the current direction.

The sub-module is bypassed and the current flows towards the next sub-module keeping the capacitor charge constant.


TABLE II FBSM MODES OF OPERATION

Mode

I

II

III

IV

V

S1

Switched on

Switched off

Switched on

Switched off

Switched off

S2

Switched off

Switched on

Switched off

Switched on

Switched off

S3

Switched off

Switched off

Switched on

Switched on

Switched off

S4

Switched on

Switched on

Switched off

Switched off

Switched off

Description

The output voltage from the sub- module has a positive polarity. The capacitor is charging or discharging, depending on the current direction.

The sub-module is bypassed and the current flows towards the next sub- module keeping the capacitor charge constant.

The output voltage from the sub- module has a negative polarity. The capacitor is charging or discharging, depending on the current direction.

The sub-module is blocked and no energy can be exchanged.


B. The HMMC Mathematical Model

To estimate the capacitor voltages of a HMMC, it is necessary to find a mathematical model of the converter. Neglecting the difference between HBSM and FBSM, the output phase voltage vo is given by [13], [14]:

그림입니다.
원본 그림의 이름: CLP00000f58000e.bmp
원본 그림의 크기: 가로 1323pixel, 세로 165pixel             (1)

그림입니다.
원본 그림의 이름: CLP00000f58000f.bmp
원본 그림의 크기: 가로 1361pixel, 세로 174pixel         (2)

where iu and il are the upper and lower arm currents, respectively, Larm is the arm inductance, marm u and marm u are the modulation values of the upper and lower arms, respectively, and ΣvCu and ΣvCl are the sums of the upper and lower arm capacitor voltages, respectively. To find the minimum number of the FBSMs needed to block DC faults, let the number of the FBSMs per arm be NF and the number of the HBSMs per arm be NH, where NNHNF is the number of sub-modules per arm. When all of the arm sub-modules are inserted, the maximum line-to-line output voltage is given by:

그림입니다.
원본 그림의 이름: CLP00000f580010.bmp
원본 그림의 크기: 가로 678pixel, 세로 188pixel      (3)

The voltage generated by the FBSMs in each arm is:

그림입니다.
원본 그림의 이름: CLP00000f580011.bmp
원본 그림의 크기: 가로 841pixel, 세로 183pixel   (4)

To successfully block any DC-side fault from transmitting to the AC-side through the converter, the FBSM voltage of the two arms, 2vFBSM arm, should be higher than the maximum line to line output voltage, vo max, which results in:

그림입니다.
원본 그림의 이름: CLP00000f580014.bmp
원본 그림의 크기: 가로 944pixel, 세로 281pixel        (5)

Rearranging (5), the number of FBSMs should satisfy the following condition:

그림입니다.
원본 그림의 이름: CLP00000f580015.bmp
원본 그림의 크기: 가로 931pixel, 세로 370pixel               (6)


C. The Switching of the HMMC using the Phase Shifted Carrier based Modulation Technique

There are many carriers based modulation techniques that can be used in the switching of HMMCs [15]-[18]. Phase shifted pulse width modulation (PS-PWM) is more suitable for this particular application due to its promising advantages such as its ease of implementation and stable performance in normal and abnormal operating conditions [15].

As shown in Fig. 2, each of the sub-modules has a devoted carrier signal with a different phase shift. The gating signals for a sub-module result from comparing its associated carrier signal with the voltage reference signal. It is worth mentioning that the phase shift between two consecutive carrier signals is calculated from:

그림입니다.
원본 그림의 이름: CLP00000f580016.bmp
원본 그림의 크기: 가로 902pixel, 세로 138pixel            (7)


그림입니다.
원본 그림의 이름: image3.png
원본 그림의 크기: 가로 610pixel, 세로 411pixel

Fig. 2. Phase shifted carrier PWM.


Ⅲ. CAPACITOR VOLTAGE ESTIMATION

The process of the capacitor voltage estimation is critical since the performance of the HMMC is fully depending on the accuracy of the estimated voltages. The proposed control system of the HMMC incorporates two capacitor voltage estimation techniques for the proposed fault detection unit. The first estimation technique is based on the ADAptive LInear NEuron (ADALINE) and the second technique is centered on the Recursive Least Squares (RLS) algorithm, which is also utilized to feedback estimated capacitor voltages to the proposed capacitor voltage balancing scheme.


A.The ADALINE Technique for Capacitor Voltages Estimation

ADALINE is an adaptive online tracking technique which is known for its unique features such as reduced calculations, improved accuracy and fast behavior [19]-[22]. To estimate the capacitor voltages, three voltage sensors are required for the estimation process. Two are used to measure the arm voltages and vLu while vLl the third is used to measure the output voltage. Rearrange the model of the HMMC, given by (1) and (2), as follows:

그림입니다.
원본 그림의 이름: CLP00000f580017.bmp
원본 그림의 크기: 가로 1277pixel, 세로 275pixel        (8)

그림입니다.
원본 그림의 이름: CLP00000f580018.bmp
원본 그림의 크기: 가로 1214pixel, 세로 272pixel           (9)

where Sxi is the switching state of the ith sub-module, the sub-suffix x = u or l for the upper or lower arm, respectively, 그림입니다.
원본 그림의 이름: CLP00000f580019.bmp
원본 그림의 크기: 가로 395pixel, 세로 116pixel, and 그림입니다.
원본 그림의 이름: CLP00000f58001a.bmp
원본 그림의 크기: 가로 364pixel, 세로 102pixel. From (8) and (9), the input vector is given by:

그림입니다.
원본 그림의 이름: CLP00000f58001b.bmp
원본 그림의 크기: 가로 1001pixel, 세로 85pixel                   (10)

While the weighting vector is:

그림입니다.
원본 그림의 이름: CLP00000f58001c.bmp
원본 그림의 크기: 가로 505pixel, 세로 264pixel                                       (11)

The actual output signal is represented by the left hand side of (8) and (9), and is given by:

그림입니다.
원본 그림의 이름: CLP00000f58001d.bmp
원본 그림의 크기: 가로 622pixel, 세로 98pixel                                     (12)

Multiplying (10) by (11) results in the predicted output signal from the ADALINE algorithm, ŷ(k)=X(k)W(k) which gives the right hand side components of (8) and (9). Consequently, the weight vector W(k) is updated by minimizing the error between the predicted ŷ(k) and the measured y(k) signals. This step is done using the Widro-Hoff delta rule given by [22]:

그림입니다.
원본 그림의 이름: CLP00000f58001f.bmp
원본 그림의 크기: 가로 991pixel, 세로 123pixel   (13)

where α is the reduction factor that is responsible for controlling the speed of the conversion. Based on many studies, α is limited to between 0 and 0.1 [23]. Once the predicted signal ŷ(k) converges to the measured signal ŷ(k), the ADALINE technique estimates the capacitors voltages. The reduced calculations of this algorithm enables the implementation of a low cost centralized controller for the HMMC with a large number of sub-modules due to the elimination of the sub-module voltage measurements and their associated communication link.


B. The RLS Technique for Capacitor Voltages Estimation

The RLS algorithm is an iterative-based on-line tracking technique, which offers stable and accurate behavior. The advantage of the RLS algorithm over other on-line tracking algorithms comes from its ability to update higher weighting vectors using the present inputs instead of the previous captured inputs, which reduces the dependency on older inputs as time passes [24], [25]. The RLS algorithm is formed by two equations. One equation is used to update the estimate vector 그림입니다.
원본 그림의 이름: CLP0000210c00ec.bmp
원본 그림의 크기: 가로 124pixel, 세로 77pixel of the sub-module capacitor voltages, as formulated in (14), and the other equation is for updating the weighting matrix P(k), as formulated in (15).

그림입니다.
원본 그림의 이름: CLP00000f580020.bmp
원본 그림의 크기: 가로 1396pixel, 세로 102pixel      (14)

그림입니다.
원본 그림의 이름: CLP00000f580021.bmp
원본 그림의 크기: 가로 1229pixel, 세로 141pixel   (15)

where ϕ(k) symbolizes the switching state vector [Sx1 Sx2 … SxN]T at time k, and λ is the forgetting factor that regulates the convergence rate. The predicted signal ŷ is calculated from 그림입니다.
원본 그림의 이름: CLP00000f580022.bmp
원본 그림의 크기: 가로 405pixel, 세로 76pixel which is subtracted from the measured signal, and the error is utilized to update the estimate vector [26]. When the prediction error diminishes, convergence is achieved and the capacitor voltages are estimated.



Ⅳ. PROPOSED HMMC CENTRALIZED CONTROLLER

The key advantage of the proposed control system for the HMMC is its capability to operate under normal and fault conditions. The proposed centralized control strategy for the HMMC integrates three main sub-control units. The three units are the capacitor voltages balancing control unit, the fault detection unit, and the fault tolerant control unit.


A. The Capacitor Voltage Balancing Control Unit

Since a fault tolerant control scheme is standard and suitable for many capacitor voltage balancing strategies, two capacitor voltage schemes are introduced to demonstrate this concept.

The first technique was developed to provide a simple method for balancing the capacitor voltages instead of depending on complex techniques which makes it suitable for a HMMC with a high number of voltage levels.

In this method, the arm current is observed to determine whether it is charging or discharging the sub-modules. In the case of charging the capacitors, the algorithm calculates the number of sub-modules that need to be inserted Nnew based on the measured capacitor voltages. Then, it calculates the difference between this number and the old number of sub-modules that is already inserted 그림입니다.
원본 그림의 이름: CLP00000f580023.bmp
원본 그림의 크기: 가로 599pixel, 세로 84pixel. If ΔNon is zero, then the switching is kept as it is and nothing changes. However, if ΔNon is greater than zero, the arm current is checked to determine whether it is charging or recharging the arm capacitors. If the arm current iarm is higher than zero, the algorithm inserts ΔNon submodules that have the lowest voltages depending on the estimation of the RLS schemes. Meanwhile the algorithm bypasses ΔNon submodules that have the highest RLS estimated voltage if iarm is less than zero. Finally, if ΔNon is lower than zero and the arm current iarm is higher than zero, the algorithm inserts ΔNon submodules that have the highest RLS estimated voltages. Meanwhile the algorithm bypasses iarm submodules that have lowest RLS estimated voltages if the iarm is less than zero [27]. This method enhances the performance of the HMMC since the converter losses are lowered due to the relatively low switching frequency. Moreover, there are no complex calculations or sophisticated Proportional Integral Derivative (PID) control loops, which make it simpler than other techniques. This scheme is used in PSCAD offline simulations.

The second scheme is formed from two main parts. The first is the averaging part, while the second is the balancing part. The averaging control is responsible for balancing the energy between two arms through regulating the average voltage of the whole leg. It includes two cascaded loops per phase to control the average voltage based on PI controllers [14]. The outer loop generates the reference of the differential current 그림입니다.
원본 그림의 이름: CLP00000f580027.bmp
원본 그림의 크기: 가로 86pixel, 세로 61pixel by managing the error between the average voltage estimated by the RLS algorithm, 그림입니다.
원본 그림의 이름: CLP00000f580024.bmp
원본 그림의 크기: 가로 368pixel, 세로 65pixel그림입니다.
원본 그림의 이름: CLP00000f580025.bmp
원본 그림의 크기: 가로 329pixel, 세로 63pixel, and the desired capacitor voltage 그림입니다.
원본 그림의 이름: CLP00000f580026.bmp
원본 그림의 크기: 가로 51pixel, 세로 48pixel, where 그림입니다.
원본 그림의 이름: CLP00000f580029.bmp
원본 그림의 크기: 가로 96pixel, 세로 54pixel is the number of effective sub-modules per arm. The inner loop sets the averaging voltage signal 그림입니다.
원본 그림의 이름: CLP00000f580028.bmp
원본 그림의 크기: 가로 78pixel, 세로 48pixel to regulate the differential current defined by 그림입니다.
원본 그림의 이름: CLP00000f58002a.bmp
원본 그림의 크기: 가로 307pixel, 세로 57pixel at its reference 그림입니다.
원본 그림의 이름: CLP00000f580027.bmp
원본 그림의 크기: 가로 86pixel, 세로 61pixel.

The balancing control is formed from N separate P-controllers to process the error between the reference and the estimated signals of the capacitor voltage. The sign of the arm current is multiplied by the actions of the P controllers to form reference signals to balance the voltage across the corresponding arm capacitors, vcul_bal, … ,vcuN_bal, vcll_bal, … , vclN_bal. Finally, the voltage balancing signal for each sub-module, the average voltage reference, 그림입니다.
원본 그림의 이름: CLP00000f58002b.bmp
원본 그림의 크기: 가로 83pixel, 세로 54pixel, and the desired phase voltage, 그림입니다.
원본 그림의 이름: CLP00000f58002c.bmp
원본 그림의 크기: 가로 51pixel, 세로 50pixel, are added together to form modulating signals for the sub-modules. The PS-PWM technique is adopted to produce switching signals for the sub-modules of the HMMC. This balancing strategy is used in the real-time simulation part.


B. The Fault Detection Unit

Fig. 3 presents the proposed fault detection unit (FDU), which is based on the percentage of the reduction in the estimated voltage and the rate of change of the deviation among the estimated voltages using the ADALINE and RLS techniques. The estimated capacitor voltages, vcxi RLS , for each sub-module i = 1,2,3…..,N using the RLS algorithm are normalized by dividing the reference capacitor voltage 그림입니다.
원본 그림의 이름: CLP00000f580026.bmp
원본 그림의 크기: 가로 51pixel, 세로 48pixel to get their per-unit values vcxi RLS pu. In addition, the deviation among the estimated capacitor voltages using ADALINE and RLS is determined for each sub-module. Hence, the rate of change of the deviation signal 그림입니다.
원본 그림의 이름: CLP00000f58002d.bmp
원본 그림의 크기: 가로 65pixel, 세로 43pixel is calculated. The proposed FDU benefit from the dynamic behavior variations among the ADALINE and RLS techniques due to their diverse objectives. If the estimated per-unit voltage for any sub-module exceeds 85%, the sub-module is considered healthy. Otherwise, if the rate of change of the deviation signal surpasses a predefined level that is set according to the desired sensitivity, the FDU registers a possible fault in the corresponding sub-module. To indicate a faulty sub-module, a counter is devoted to ensure the constancy of the estimated signals for a given amount of time. Finally, the FDT set flags for the faulty sub-modules that are accessed by the fault tolerant control unit.


그림입니다.
원본 그림의 이름: image4.png
원본 그림의 크기: 가로 721pixel, 세로 207pixel

Fig. 3. Block diagram of the proposed fault detection unit.


The hybrid decision making of the proposed FDU results in robust performance. In addition, no extra circuits or components are required since the proposed FDU employs estimation algorithms that are already developed for the proposed control of the HMMC.


C. The Fault Tolerant Control Unit

The main tasks of the proposed fault tolerant control unit (FTCU) are to disconnect faulty sub-modules and to modify the capacitor voltage balancing unit. The proposed FTCU utilizes the flags of faulty sub-modules set by the FDU to define the number of faulty sub-modules Nxf. For a faulty sub-module in the upper arm, the FTCU isolates it with one in the lower arm. Bypass switches are used to isolate sub-modules. To keep the balance between the upper and lower arms, a healthy sub-module in the adjacent arm is isolated to make the number of activate sub-modules in the two arms equal. Consequently, the reference capacitor voltage 그림입니다.
원본 그림의 이름: CLP00000f580026.bmp
원본 그림의 크기: 가로 51pixel, 세로 48pixel is increased by 그림입니다.
원본 그림의 이름: CLP00000f58002e.bmp
원본 그림의 크기: 가로 186pixel, 세로 75pixel to substitute for the reduction of active sub-modules. Simultaneously, the proposed FTCU adapts the phase shift of the carrier signals for the active sub-modules of the leg according to (3).

The proposed fault tolerant strategy allows a HMMC to continue operation if the number of faulty sub-modules does not exceed a certain percentage and there is no external DC short circuit. Otherwise, the control system should block all of the FBSMs and deactivate the converter. The maximum percentage of faulty sub-modules per arm is selected based on the number of sub-modules per arm and the ratings of the power electronic devices. For example, for the eight level MMC used in the simulation, the maximum percentage of faulty sub-modules per arm can be 25%. Increasing the number of voltage levels, decreases the allowable percentage of faulty sub-modules.

It is clear that the proposed control strategy avoids the need for an enormous numbers of voltage sensors for the sub- module capacitors and their correlated communication links with the central controller. As a result, the proposed control strategy renders its implementation for an HMMC with many sub-modules.



Ⅴ. OFFLINE SIMULATION RESULTS

Unlike the detailed model presented in the previous subsection, an average model of a 77-level MMC is considered to facilitate calculations due to the relatively high number of sub-modules. The average model used in the simulation depends on converting the detailed model of the sub-module into its Thevenin equivalent [28]. As shown in Fig. 4, the model contains two wind farms, where each has a rating of 500 MW. The first wind farm delivers energy through a permanent magnet synchronous generator (PMSG), and the output voltage of the PMSG is 0.69 kV. The terminals of the PMSG are connected to a back-to-back two-level VSC.


그림입니다.
원본 그림의 이름: image5.png
원본 그림의 크기: 가로 833pixel, 세로 799pixel

Fig. 4. Circuit diagram of the second MMC model.


The generator used in the second wind farm is a double-fed induction generator (DFIG), which generates power at 0.69 kV. The rotor winding of the DFIG is connected to a back-to-back two-level VSC. The output of this VSC and the stator winding of the DFIG are both connected to a three-core transformer. Since both of the wind farms are working on the same voltage level, a point of common coupling is formed, which connects the two wind farms together with the rectifier stage of the HVDC. The HVDC link is formed from two MMCs connected through a 200 kM cable. The output of the inverter stage of the HVDC system is connected to a 220 kV AC grid.

The rated power of both MMCs is selected to be 1,000 MW, while the rated DC voltage is 640 kV. The size of the sub-module capacitor is calculated in the same manner as presented in the previous subsection. Table III shows the parameters of the offline simulation model.


TABLE III HMMC GRID CONNECTED MODEL PARAMETERS

HMMC Model Parameters

Rated power

500 MW

Sub-module rated voltage

4.2 kV

Rated dc Voltage

640 kV

Arm inductance

70 mH

Sub-module capacitance

220 µF

Number of HBSM per leg

4

Number of FBSM per leg

152


The simulated case is developed to evaluate the proposed capacitor voltage estimation technique, when applied to an HMMC-based HVDC system that integrates offshore wind power with the grid. It was also developed to investigate the accuracy of the proposed capacitor voltage estimation techniques for an HMMC with a relatively high number of voltage levels. Furthermore, the dynamic performance of the proposed capacitor voltage estimation technique is assessed under external grid faults. The RLS capacitor voltage estimation technique provides it with estimated capacitor voltages instead of using direct measurements. This is done to prove that the proposed RLS capacitor voltage estimation can be adopted for different capacitor voltage balancing techniques. In this case, the reference DC voltage signal is 640 kV. Then, at t = 6 s, a three-phase fault is applied at the grid side, which lasts for 0.2 s. The capacitor voltage estimation-based voltage balancing technique succeeds in balancing the capacitor voltages, as shown in the balanced three-phase voltages presented in Fig. 5. The RLS estimation algorithm provided balancing control over the whole period even during the external fault period. Fig. 6(a) and (b) illustrate the summation of the capacitor voltages of the upper and lower arms. Moreover, the capacitor voltages of one sub-module from the upper and lower arms are portrayed in Fig. 6(c) and (d), respectively. They follow the traces of the actual capacitor voltages of the upper and lower arms, even during a grid fault. Results obtained in this case prove that the proposed capacitor voltage estimation algorithm is not affected by external AC faults or grid power controls. Therefore, the proposed capacitor voltage estimation algorithm is suitable for HMMCs with a high number of voltage levels, which are normally used in HVDC circuits.


그림입니다.
원본 그림의 이름: CLP00000f58002f.bmp
원본 그림의 크기: 가로 1166pixel, 세로 564pixel

Fig. 5. Grid voltages [28].


그림입니다.
원본 그림의 이름: CLP00000f580030.bmp
원본 그림의 크기: 가로 1141pixel, 세로 703pixel

Fig. 6. Actual and estimated sub-module capacitor voltages in leg a: (a) summation of the capacitor voltages in the upper arm; (b) summation of the capacitor voltages in the lower arm; (c) capacitor voltage of one sub-module in the upper arm; (d) capacitor voltage of one sub-module in the lower arm [28].


Ⅵ. HARDWARE IN THE LOOP OF THE SIMULATION RESULTS

Validation of the proposed control scheme for a HMMC is done using the concept of hardware in the loop (HIL) of the simulation through the incorporation of an OPAL-RT type OP4510 real-time digital simulator with a NI type cRIO-9024 real-time physical FPGA as illustrated in Fig. 7. The HMMC model is simulated using the real-time digital simulator including the whole network with the support of the RT-LAB software, the DC supply and the AC system. Meanwhile, the proposed HMMC centralized controller is programmed on the FPGA using LABVIEW software. The real-time digital simulator provides the FPGA controller with the values of the output and arm voltages through its analog outputs. Meanwhile, the FPGA controller provides the simulator with gating signals through its digital outputs. Moreover, the FPGA controller estimates the capacitor voltages required for the balancing control unit and the FDU. It also executes the proposed FTCU. The system parameters are given in Table IV.


그림입니다.
원본 그림의 이름: ㅂㅂ.jpg
원본 그림의 크기: 가로 1074pixel, 세로 532pixel
사진 찍은 날짜: 2018년 11월 26일 오후 4:24

Fig. 7. HIL platform.


TABLE IV HMMC MODEL PARAMETERS

HMMC Model Parameters

Rated power

1 MW

Sub-module rated voltage

2250 V

Rated dc Voltage

9000 V

Arm inductance

3 mH

Sub-module capacitance

1900 µF

Number of HBSM per leg

4

Number of FBSM per leg

4

Load impedance

30 Ω , 6 mH


The simulated HMMC has four HBSMs and four FBSMs to satisfy (6). Different operation scenarios are considered to assess the performance of the proposed strategy for the HMMC. Moreover, the dynamic performance of the proposed FDU is examined under various healthy and faulty conditions. The first case study is devoted to examining the performance of the proposed control system for the HMMC using the RLS algorithm for capacitor voltage estimations. The second task is dedicated to evaluating the dynamic performance of the proposed FDU and the FTCU.


A. Performance of the Proposed Capacitor Voltage Estimation Based Control Strategy

This case is devoted to examining the dynamic performance of the proposed capacitor voltage estimation based control algorithm for the HMMC under a dynamic change of the reference phase voltage. The reference capacitor voltage 그림입니다.
원본 그림의 이름: CLP00000f580026.bmp
원본 그림의 크기: 가로 51pixel, 세로 48pixel is set at vdc/N = 2.25KV, while the reference phase voltage signal 그림입니다.
원본 그림의 이름: CLP0000210c0001.bmp
원본 그림의 크기: 가로 63pixel, 세로 62pixel is dynamically changed from 0.7pu to 1pu. The measured three-phase ac voltages follow their reference signals, as illustrated in Fig. 8(a). At the beginning, when 그림입니다.
원본 그림의 이름: CLP00000f580031.bmp
원본 그림의 크기: 가로 194pixel, 세로 40pixel, six sub-modules are utilized and when 그림입니다.
원본 그림의 이름: CLP00000f580032.bmp
원본 그림의 크기: 가로 165pixel, 세로 43pixel, and all of the sub-modules are encompassed. Fig. 8(b) displays the three-phase load currents. Fig. 8(c) and 8(d) show the capacitor voltages that are grouped in two main trajectories, one for the upper arm and the other for the lower arm. The proposed HMMC controller is able to balance the capacitor voltages at their reference value of 2.25 KV. Moreover, Fig 9 (a) shows the estimated capacitor voltage of the first sub-module, and compares it with its corresponding actual voltage. The fast tracking and accurate performance of the proposed scheme based on the RLS algorithm for estimating the sub-modules capacitor voltages are evident. Furthermore, the circulating current closely follows its reference signal as demonstrated in Fig. 9(b). Fig. 9(c) and Fig. 9(d) illustrate the actions of the averaging controller and the balancing controller for the first sub-module in the upper arm 그림입니다.
원본 그림의 이름: CLP0000210c0002.bmp
원본 그림의 크기: 가로 193pixel, 세로 71pixel, respectively. These results reveal the efficient utilization of the proposed capacitor voltage estimation scheme for the control algorithm of the HMMC.


Fig. 8. Enabling the proposed estimation unit: (a) three-phase voltages; (b) three-phase load currents; (c) sub-module voltages of the upper arm of leg a; (d) sub-module voltages of the lower arm of leg a.

그림입니다.
원본 그림의 이름: image9.png
원본 그림의 크기: 가로 728pixel, 세로 475pixel

(a)

 

그림입니다.
원본 그림의 이름: image10.png
원본 그림의 크기: 가로 727pixel, 세로 475pixel

(b)

 

그림입니다.
원본 그림의 이름: image11.png
원본 그림의 크기: 가로 728pixel, 세로 474pixel

(c)

 

그림입니다.
원본 그림의 이름: image12.png
원본 그림의 크기: 가로 726pixel, 세로 474pixel

(d)


Fig. 9. Performances of different controllers: (a) voltage of the first sub-module; (b) circulating current; (c) averaging voltage reference; (d) modulating signal for the first sub-module of the upper arm of leg a.

그림입니다.
원본 그림의 이름: image13.png
원본 그림의 크기: 가로 684pixel, 세로 429pixel

(a)

 

그림입니다.
원본 그림의 이름: image14.png
원본 그림의 크기: 가로 728pixel, 세로 472pixel

(b)

 

그림입니다.
원본 그림의 이름: image15.png
원본 그림의 크기: 가로 725pixel, 세로 474pixel

(c)

 

그림입니다.
원본 그림의 이름: image16.png
원본 그림의 크기: 가로 729pixel, 세로 473pixel

(d)


B. Performance Under an Open Switch Fault

This task is dedicated to evaluate the potential of the proposed control system, the FDU, and the FTCU under an open switch fault in a sub-module. To simulate an open switch fault, the upper switch of the third sub-module in the upper arm of phase a is purposely opened. Fig 10 indicates that the proposed FDU manages to detect and localize the sub-module fault after 35.6 ms. Considering the rate of change of the capacitors voltages, a 35.6 ms detection period is sufficient to secure the operation of the HMMC. Once the faulty sub-module is detected, the FTCU disconnects it with a sub-module in the lower arm to balance the voltages of the two arms.


그림입니다.
원본 그림의 이름: image17.png
원본 그림의 크기: 가로 727pixel, 세로 190pixel

Fig. 10. Dynamic performance of the proposed FDU under an open switch fault


Moreover, the FTCU boosts 그림입니다.
원본 그림의 이름: CLP00000f580026.bmp
원본 그림의 크기: 가로 51pixel, 세로 48pixel from 2250 V to 3000 V, and modifies the carrier phase shift to 60º instead of 45º to account for the two disconnected sub-modules. These arrangements are adequate for fault tolerance and to sustain the operation of the HMMC as indicated from Fig. 11, where the three-phase voltages and currents are balanced. Fig. 12 demontrates that the capacitor voltages of the activated sub-modules reinstate their balance at the new set value of the FTCU. As expected, the disconnected sub-modules have constant capacitor voltages. The capacitor voltage estimation unit succeeds in estimating the voltage even under an open switch fault for all of the healthy sub-modules as illustrated in Fig. 13(a). As shown in Fig. 13(b), the RLS estimated signal for the faulty sub-module is accurate until the instant of interruption.


Fig. 11. Waveforms under an open switch fault: (a) three-phase voltages; (b) three-phase load currents.

그림입니다.
원본 그림의 이름: image18.png
원본 그림의 크기: 가로 728pixel, 세로 497pixel

(a)

 

그림입니다.
원본 그림의 이름: image19.png
원본 그림의 크기: 가로 729pixel, 세로 476pixel

(b)


Fig. 12. Waveforms under an open switch fault: (a) sub-modules voltages of the upper arm in leg a; (b) sub-modules voltages of the lower arm in leg a.

그림입니다.
원본 그림의 이름: image20.png
원본 그림의 크기: 가로 726pixel, 세로 479pixel

(a)

 

그림입니다.
원본 그림의 이름: image21.png
원본 그림의 크기: 가로 729pixel, 세로 473pixel

(b)


Fig. 13. RLS estimated signals in the upper arm of leg a under an open switch fault: (a) first sub-module (healthy); (b) third sub-module (faulty).

그림입니다.
원본 그림의 이름: image22.png
원본 그림의 크기: 가로 728pixel, 세로 474pixel

(a)

 

그림입니다.
원본 그림의 이름: image23.png
원본 그림의 크기: 가로 727pixel, 세로 473pixel

(b)


The ADALINE and RLS algorithms provide the FDU and the FTCU with accurate data that results in precise performance during transient periods. Fig. 14(a) reveals that the actions of the proposed FTCU results in limiting the differential current to its pre-fault setting. In addition, the averaging control loop succeeds in overcoming the consequences of the fault as indicated in Fig. 14(b). Moreover, the balancing control signal is quickly stabilized as manifested from the modulating signal of the first sub-module in the upper arm of leg a as shown in Fig. 14(c).


Fig. 14. Performance of different controllers under an open switch fault: (a) circulating current; (b) averaging voltage reference; (c) modulating signal for the first sub-module of the upper arm of leg a.

그림입니다.
원본 그림의 이름: image24.png
원본 그림의 크기: 가로 728pixel, 세로 474pixel

(a)

 

그림입니다.
원본 그림의 이름: image25.png
원본 그림의 크기: 가로 724pixel, 세로 473pixel

(b)

 

그림입니다.
원본 그림의 이름: image26.png
원본 그림의 크기: 가로 727pixel, 세로 474pixel

(c)


C. Performance Under a Sub-module Short Circuit Fault

This task is devoted to the assessment of the dynamic performance of the proposed strategy under a short circuit fault in a sub-module. The upper switch of the third sub-module in the upper arm of phase a is closed to simulate a short circuit fault. The FDU detects and localizes the fault after 3.2 ms as shown in Fig 15. The detection time is very fast especially since short circuit faults are very destructive and needs to be cleared quickly. Consequently, the FTCU disconnects the faulty sub-module along with another one from the lower arm to sustain the voltage balance of the two arms. As in a pen switch fault, the FTCU modifies 그림입니다.
원본 그림의 이름: CLP00000f580026.bmp
원본 그림의 크기: 가로 51pixel, 세로 48pixel and the carrier phase shift. These procedures are obligatory to keep the operation of the HMMC as indicated from the results in Fig. 16. The capacitor voltages of the effective sub-modules are balanced at a new boost setting by the FTCU as illustrated in Fig. 17 (a) and (b) for the upper arm and lower arm sub-modules, respectively. The capacitor voltage estimation unit succeeds in estimating a voltage even in the case of a short circuit fault as shown in Fig. 18. Fig. 18 (b) shows the estimated signal of the faulty sub-module. The differential current, averaging and voltage balancing signals are quickly stabilized as shown in Fig. 19.


그림입니다.
원본 그림의 이름: image27.png
원본 그림의 크기: 가로 729pixel, 세로 192pixel

Fig. 15. Dynamic performance of the proposed FDU under a short circuit fault in a sub-module.


Fig. 16. Waveforms under a short circuit fault: (a) three-phase voltages; (b) three-phase load currents.

그림입니다.
원본 그림의 이름: image28.png
원본 그림의 크기: 가로 727pixel, 세로 497pixel

(a)

 

그림입니다.
원본 그림의 이름: image29.png
원본 그림의 크기: 가로 728pixel, 세로 474pixel

(b)


Fig. 17. Waveforms under a short circuit fault: (a) sub-module voltages of the upper arm in leg a; (b) sub-module voltages of the lower arm in leg a.

그림입니다.
원본 그림의 이름: image30.png
원본 그림의 크기: 가로 728pixel, 세로 475pixel

(a)

 

그림입니다.
원본 그림의 이름: image31.png
원본 그림의 크기: 가로 730pixel, 세로 476pixel

(b)


Fig. 18. RLS estimated signals in the upper arm of leg a under a short circuit: (a) first sub-module (healthy); (b) third sub-module (faulty).

그림입니다.
원본 그림의 이름: image32.png
원본 그림의 크기: 가로 728pixel, 세로 474pixel

(a)

 

그림입니다.
원본 그림의 이름: image33.png
원본 그림의 크기: 가로 728pixel, 세로 474pixel

(b)


Fig. 19. Performance of different controllers under a short circuit fault: (a) circulating current; (b) averaging voltage reference; (c) modulating signal for the first sub-module of the upper arm of leg a.

그림입니다.
원본 그림의 이름: image24.png
원본 그림의 크기: 가로 728pixel, 세로 474pixel

(a)

 

그림입니다.
원본 그림의 이름: image25.png
원본 그림의 크기: 가로 724pixel, 세로 473pixel

(b)

 

그림입니다.
원본 그림의 이름: image26.png
원본 그림의 크기: 가로 727pixel, 세로 474pixel

(c)


D. Practical Assessment of the Proposed Techniques

The main aim of building a HIL platform is its ability to assess any proposed control technique by determining whether or not it can be implemented industrially. In addition, the use of HIL simulations ascertains the feasibility of any developed algorithms. In terms of the proposed techniques for the HMMC inner control, fault detection and tolerant control algorithms, the great challenge in implementing these control functions is the required computational volume, since all of the tasks depend on the estimation of the capacitor voltages for all of the sub-modules, which may total at least 800 per leg. If the computational burden is too high, a computer with a very large processor is required. In this case the control technique would require code optimization and several reductions in the calculations. For this purpose, the computational burden of the simulated HMMC is presented. Based on this a conception is shown for a real HMMC project with 800 sub-modules per arm. The computational burden can be calculated with the number of logical resources consumed inside the FPGA. The building unit of an FPGA is its lookup table (LUT). The 4-input LUT is a small piece of RAM that is connected in the form of combinational logic to perform a specific function. The relationship between the 4 inputs and the outputs are simply a truth table, which is built through a synthesizing process.

The implementation of the proposed control on a cRIO virtex 5 based FPGA controller for controlling a HMMC with 8 modules per arm consumed 19,872 LUTs, with the physical controller having an embedded FPGA system with a maximum number of 28800 LUTs, which means that only 70% of the FPGA’s resources are utilized. This means that when selecting a controller for an HMMC with 800 sub-modules per leg, applying the proposed control technique requires 1,987,200 LUTs. This can easily be achieved by using a VIRTEX 7s three FPGA controller, which has 2,000,000 LUTs inside its processing unit. Therefore, 99% of the logic capacity of the controller is utilized, which means the proposed control techniques can be implemented practically in terms of its computational burden.



Ⅶ. CONCLUSION

This paper presents a control scheme for the HMMC that does not need to sense the capacitor voltages to balance the DC voltages between sub-modules. A model of the HMMC is derived for the estimation of the capacitor voltages from the measured phase voltage, the arm reactors voltages, and the switching signals. An estimation unit is proposed for the capacitor voltages based on the RLS algorithm. Moreover, a hybrid estimation unit based on the ADALINE and RLS techniques for without sensing capacitor voltages of sub- modules is adopted to detect and identify faulty sub-modules. Furthermore, a FTCU is proposed to boost the capacitor voltages and to adjust the shift angles between carrier signals after isolating the faulty sub-modules to deal with the reduced number of effective sub-modules. One advantage of the proposed centralized strategy is the elimination of the sensors used to measure capacitors voltages and their required communication link. This action renders the proposed control scheme suitable for implementation with a low cost centralized controller for the HMMC. Additionally, the proposed FTCU does not require further elements. A real-time digital simulator connected to a physical controller is utilized to investigate the dynamic response of the proposed control system. The accurate performance and fast response of the proposed units for sub-modules capacitor voltage estimation are revealed from the results under different dynamic conditions. In addition, the proposed centralized strategy manages to balance the capacitors voltages. Furthermore, the circulating current follows its reference signal. The accurate operation of the proposed hybrid estimation based FDU results from the fact that decisions are based on the magnitude and rate of the change in the deviation among the estimated voltages from the proposed ADALINE and RLS techniques. Finally, the obtained results demonstrate the ability of the integrated FTCU to stabilize the operation of the HMMC under different fault conditions.



REFERENCES

[1] S. Debnath, J. Qin, B. Bahrani, M. Saeedifardand, and P. Barbosa, “Operation, control, and applications of the modular multilevel converter: A review,” IEEE Trans. Power Electron., Vol. 30, No. 1, pp. 37-53, Jan. 2015.

[2] W. Li, L. Gregoire, and J. Bélanger, “Control and performance of a modular multilevel converter system,” in Proc. CIGRÉ Canada Conference on Power Systems, pp. 1-8, 2011.

[3] Y. Wan, S. Liu, and J. Jiang, “Generalized analytical methods and current-energy control design for modular multilevel cascade converter,” IET Power Electron., Vol. 6, No. 3, pp. 495-504, Mar. 2013.

[4] R. Zeng, L. Xu, L. Yao, and B. W. Williams, “Design and operation of a hybrid modular multilevel converter,” IEEE Trans. Power Electron., Vol. 30, No. 3, pp. 1137-1146, Mar. 2015.

[5] A. Beddard, M. Barnes, and R. Preece, “Comparison of detailed modeling techniques for MMC employed on VSC-HVDC schemes,” IEEE Trans. Power Del., Vol. 30, No. 2, pp. 579-589, Apr. 2015.

[6] O. Kaijian, R. Hong, C. Zexiang, G. Haiping, L. Xuehua, G. Lin, M. Trevor, W. Bruce, and C. Yuan, “MMC-HVDC simulation and testing based on real-time digital simulator and physical control system,” IEEE J. Emerg. Sel. Topics Power Electron., Vol. 2, No. 4, pp. 1109-1116, Dec. 2014.

[7] S. Xu and A. Huang, “Circulating current control of double-star chopper cell modular multilevel converter for HVDC system,” in Proc. Annual Conference on IEEE Industrial Electronics Society (IECON), pp. 1234-1239, Oct. 2012.

[8] L. Hui,  L. C. Poh, and F. Blaabjerg, “Review of fault diagnosis and fault-tolerant control for modular multilevel converter of HVDC,” in Proc. IECON, pp. 1242-1247, Nov. 2013.

[9] W. Zhang, D. Xu, P. N. Enjeti, H. Li, J. T. Hawke, and H. S. Krishnamoorthy, “Survey on fault-tolerant techniques for power electronic converters,” IEEE Trans. Power Electron., Vol. 29, No. 12, pp. 6319-6331, Dec. 2014.

[10] R. Wu, F. Blaabjerg, H. Wang, M. Liserre, and F. Iannuzzo, “Catastrophic failure and fault-tolerant design of IGBT power electronic converters-An overview,” in Proc. IECON, pp. 507-513, Nov. 2013.

[11] M. Salehifar, M. Moreno-Eguilaz, G. Putrus, and P. Barras, “Simplified fault tolerant finite control set model predictive control of a five-phase inverter supplying BLDC motor in electric vehicle drive,” Electric Power Systems Research, Vol. 132, pp. 56-66, Mar. 2016.

[12] G. T. Son, H.-J. Lee, T. S. Nam, Y.- H. Chung, U.-H. Lee, S.-T. Baek, K. Hur, and J.-W. Park, “Design and control of a modular multilevel HVDC converter with redundant power modules for noninterruptible energy transfer,” IEEE Trans. Power Del., Vol. 27, No. 3, pp. 1611-1619, Jul. 2012.

[13] M. Abdelsalam, M. I. Marei, and S. Tennakoon, “An integrated control strategy with fault detection and tolerant control capability based on capacitor voltage estimation for modular multilevel converters,” IEEE Trans. Ind. Appl., Vol. 53, No. 3, pp. 2840-2851, May/Jun. 2017.

[14] A. Antonopoulos, L. Angquist, and H.-P. Nee, “On dynamics and voltage control of the modular multilevel converter,” in Proc. European Conference on Power Electronics and Applications (EPE), pp. 1-10, 2009.

[15] G. S. Konstantinou and V. G. Agelidis, “Performance evaluation of half-bridge cascaded multilevel converters operated with multicarrier sinusoidal PWM techniques,” in Proc. IEEE Conference on Industrial Electronics and Applications (ICIEA), pp. 3399-3404, 2009.

[16] A. Hassanpoor, S. Norrga, H.-P. Nee, and L. Angquist, “Evaluation of different carrier-based PWM methods for modular multilevel converters for HVDC application,” in Proc. IECON, pp. 388-393, 2012.

[17] D.-W. Kang, W.-K. Lee, and D.-S. Hyun, “Carrier-rotation strategy for voltage balancing in flying capacitor multilevel inverter,” IET Proceedings on Electric Power Applications, Vol. 151, No. 2, pp. 239-248, Mar. 2004.

[18] B.-S. Jin, W.-k Lee, T.-J. Kim, D.-W. Kang, and D.-S. Hyun, “A study on the multi-carrier PWM methods for voltage balancing of flying capacitor in the flying capacitor multi-level inverter,” Proc. IECON, pp. 1-6, 2005.

[19] M. I. Marei, E. F. El-Saadany, and M. M. A. Salama, “Experimental evaluation of envelope tracking techniques for voltage disturbances,” Electric Power System Research, Vol. 80, No. 3, pp. 339-344, Mar. 2010.

[20] M. I. Marei, A. Mohy, and A. A. El-Sattar “An integrated control system for sparse matrix converter interfacing PMSG with the grid,” International Journal of Electrical Power & Energy Systems, Vol. 73, pp. 340-349, Dec. 2015.

[21] M. Abdelsalam, M. I. Marei, S. Tennakoon, and A. Griffiths, “Capacitor voltage balancing strategy based on sub-module capacitor voltage estimation for modular multilevel converters,” CSEE Journal of Power and Energy Systems, Vol. 2, No. 1, pp. 65-73, Mar. 2016.

[22] B. Widrow and M. A. Lehr, “30 years of adaptive neural networks: perceptrons, madaline and backpropagation” IEEE Proc., Vol. 78, No. 9, pp. 1415-1442, Sep. 1990.

[23] S. Hui and S. H. Zak, “Robust stability analysis of adaptation algorithms for single perceptron,” IEEE Trans. Neural Netw., Vol. 2, No. 2, pp. 325-328, Mar. 1991.

[24] R. Johansson, System Modeling and Identification, Prentice-Hall, 2nd Edition, 1993.

[25] L. Ljung, System Identification: Theory for the User, Prentice-Hall, 1999.

[26] M. Hagiwara and H. Akagi, “Control and experiment of pulse width-modulated modular multilevel converters,” IEEE Trans. Power Electron., Vol. 24, No. 7, pp. 1737-1736, Jul. 2009.

[27] Y. Tang, L. Ran, O. Alatise, and P. Mawby, “Capacitor selection for modular multilevel converter,” IEEE Trans. Ind. Appl., Vol. 52, No. 4, pp. 3279-3293, Jul./Aug. 2016.

[28] M. F. Moussa, H. Y. Diab, and M. O. Abdelsalam, “A modified reduced frequency capacitor voltage balancing strategy with reduced number of sensors for modular multilevel converters,” in Proc. International Conference on Electrical and Electronic Engineering (ICEEE), pp. 52-55, 2017.



그림입니다.
원본 그림의 이름: image34.jpg
원본 그림의 크기: 가로 339pixel, 세로 340pixel

Mahmoud Abdelsalam received his B.S. (Honors) and M.S. degrees from the Arab Academy for Science and Technology, Cairo, Egypt, in 2008 and 2011, respectively; and his Ph.D. degree from Staffordshire University, Stoke-on-Trent, ENG, UK, in 2016. He is presently working as an Assistant Professor in the Department of Electrical Energy Engineering, College of Engineering and Technology, Arab Academy for Science and Technology, Smart Village, Egypt. He is also working as a Consultant for many international firms that develop projects in the fields of electrical power and energy. His current research interests include power system protection, renewable energy technologies, the application of power electronics in power systems and control systems technologies.


그림입니다.
원본 그림의 이름: image35.jpeg
원본 그림의 크기: 가로 193pixel, 세로 267pixel

Mostafa Ibrahim Marei received his B.S. (Honors) and M.S. degrees in Electrical Engineering from Ain Shams University, Cairo, Egypt, in 1997 and 2000, respectively; and his Ph.D. degree in Electrical Engineering from the University of Waterloo, Waterloo, ON, Canada, in 2004. From 2004 to 2006, he was a Postdoctoral Fellow at the University of Waterloo. He is presently working as a Professor in the Department of Electrical and Control Engineering, College of Engineering and Technology, Arab Academy for Science, Technology and Maritime Transport (AASTMT), Cairo, Egypt. He is presently on leave from the Department of Electrical Power and Machines, Faculty of Engineering, Ain Shams University. His current research interests include power electronics, distributed and renewable power generation, microgrids, power quality, custom power, electrical drives and artificial intelligent applications in power systems. Dr. Marei holds the State Incentive Award in Engineering Sciences, Academy of Scientific Research and Technology, Egypt. His biography is listed in Marquis Who’s Who in the World.


그림입니다.
원본 그림의 이름: image37.png
원본 그림의 크기: 가로 189pixel, 세로 269pixel

Hatem Yassin Diab received his B.S. (Honors) and M.S. degrees from the Arab Academy for Science and Technology, Cairo, Egypt, in 2009 and 2012, respectively; and his Ph.D. degree from Staffordshire University, Stoke-on-Trent, ENG, UK, in 2016. He is presently acting as Head of the Department of Electrical Energy Engineering, College of Engineering and Technology, Arab Academy for Science and Technology, Smart Village, Cairo, Egypt. His current research interests include power systems, control systems, automation, renewable energy technologies, HVDCs, DC grids and the application of power electronics in power systems. 


그림입니다.
원본 그림의 이름: image36.jpeg
원본 그림의 크기: 가로 150pixel, 세로 150pixel
사진 찍은 날짜:

Sarath B. Tennakoon received his B.S. degree in Electrical Engineering from the University of Moratuwa, Moratuwa, Sri Lanka; his M.S. degree in Electrical Engineering from the University of Aston, Birmingham, ENG, UK; and his Ph.D. degree in Electrical Engineering and Electronics from the University of Central Lancashire, Lancashire, ENG, UK. He is presently working as a Professor of Power Electronic Systems and as the Director of the Centre for Energy Efficient Systems, Staffordshire University, Stoke-on-Trent, ENG, UK. His current research interests include DC grids and HVDCs, power system protection, power electronics and harmonics.