Design Methodology of Passive Damped LCL Filter Using Current Controller for Grid-Connected Three-Phase Voltage-Source Inverters


Jun-Young Lee*, Young-Pyo Cho**, Ho-Sung Kim***, and Jee-Hoon Jung


†,*School of Electrical Engineering, Ulsan National Institute of Science and Technology, Ulsan, Korea

**Smart-Grid Group Power Distribution Lab, KEPCO Research Institute, Daejeon, Korea

***Power Conversion and Control Research Center, HVDC Research Division, KERI, Changwon, Korea



Abstract

In grid-connected voltage-source inverters (VSIs), when compared with a simple inductive L filter, the LCL filter has a better performance in attenuating the high frequency harmonics caused by the pulse-width modulation of power switches. However, the resonance peaks generated by the filter inductors and capacitors can make a system unstable. In terms of simplicity and filter design cost, a passive damping method is generally preferred. However, its high power loss and degradation in high frequency harmonic attenuation are significant demerits. In this paper, a mathematical design solution for a passive LCL filter to derive filter parameters suppressing the high frequency current harmonics to 0.3% is proposed. The minimum filter inductance can be obtained to reduce the size of the filter. Furthermore, a minimum damping resistance design considering a current controller is analyzed for a stable closed-loop system. The proposed design method is verified by experimental results using a 5-kW three-phase prototype inverter.


Key words: Current control, LCL filters, Passive damping, Stability analysis, Voltage-source inverters


Manuscript received Aug. 17, 2017; accepted Apr. 16, 2018

Recommended for publication by Associate Editor M. P. Kazmierkowski.

Corresponding Author: jhjung@unist.ac.kr, jung.jeehoon@gmail.com Tel: +82-52-217-2140, Fax: +82-52-217-2109, UNIST

*School of Electrical and Computer Engineering, UNIST, Korea

**Smart-Grid Group Power Distribution Lab, KEPCO Research Institute, Korea

***Power Conversion and Control Research Center, HVDC Research Division, KERI, Korea



Ⅰ. INTRODUCTION

In grid-connected voltage-source inverters (VSI), the excessive current harmonics caused by the pulse-width modulation (PWM) of power switches should be limited. The current harmonic limitations are specified in the IEEE-519 standard [1]. For safety issues, disturbances caused by current harmonics should be avoided so they do not affect other loads connected to the same grid. In order to attenuate current harmonics, input filters such as the simple inductive L and the LCL combination structure are widely used in grid-connected inverter applications [2]. In the conventional L filter, a high filter inductance should be used to satisfy current harmonic standards which may increase the size and cost of the filter.

To overcome this problem, the LCL filter has been proposed, as shown in Fig. 1, to achieve better attenuating performance against the current harmonics. It has a smaller filter inductance than the L filter. However, the LCL filter generates a resonance peak caused by the L and C resonant network. It can make the closed-loop system unstable, which results in a divergence of the output current. To suppress the resonance peak, various damping methods have been proposed such as active damping methods [3]-[11], passive damping methods [12]-[18], and hybrid damping methods [19], [20]. The active damping methods include single-loop methods and multi-loop methods, which use digital filters such as notch filters and additional feedback loops. However, both methods require complex control techniques, and multi-loop methods also require additional sensors. The passive damping methods use a passive damping resistor, which is a simple method that guarantees a high damping robustness. However, due to the damping resistor, there are additional power losses and performance degradation in high frequency harmonic attenuation. Alternately, the hybrid methods combine active and passive methods to reduce the power losses and improve the damping robustness. Consequently, in order to use passive damping methods that feature the simplest configuration, precise and detailed design guides are required to minimize side effects.


그림입니다.
원본 그림의 이름: image1.png
원본 그림의 크기: 가로 800pixel, 세로 349pixel

Fig. 1. Structure of an LCL filter for grid-connected three-phase inverters.


Previous studies of passive damping methods [12]-[18] presented various ways to design filter parameters such as inductors, capacitors and damping resistors. However, these methods do not present mathematical solutions to directly derive filter parameters that can suppress high frequency current harmonics to 0.3%, as specified by the IEEE-519. Therefore, it is hard to minimize the filter parameters. The authors of [6]-[8] show mathematical approaches to designing the high frequency current harmonics. However, damping resistors are not considered, which is a significant issue affecting the high frequency attenuation, the power loss and the stability issues.

This paper presents a mathematical design solution for passive LCL filters to directly derive optimal filter parameters that can suppress the high frequency current harmonics to 0.3%. In addition, by using this design solution, the minimum inductance can be derived to satisfy the IEEE-519 regulations, which can reduce the size of the filter. Furthermore, the power loss of the LCL filter is analyzed to show that it is reduced by the minimum filter inductance. In addition, a stable current controller is designed considering the damping resistor. The minimum damping resistance can be mathematically derived to obtain lower power loss, less performance degradation in the high frequency harmonic attenuation, and enough of a gain and phase margin of the current controller, which can guarantee the stable operation of the closed-loop system.

This paper is organized as follows. In Section II, a mathematical approach to derive the magnitudes of the current harmonics and the power loss is presented. In Section III, an IMC is used to design a current controller, and the minimum damping resistance is obtained. In Section IV, an analytical design methodology is presented, which is based on the mathematical analysis presented in Sections II and III. In Section V, experimental results using a 5-kW prototype three-phase inverter verify the validity and performance of the proposed design methodology.



Ⅱ. ANALYSIS OF A PASSIVE LCL FILTER MODEL

In this Section, the passive LCL filter circuit is analyzed and the magnitude of the grid-side current harmonics is mathematically derived. A theoretical method to satisfy the IEEE-519 standard is presented. Finally, the power loss in an LCL filter is analyzed to be expressed in a mathematical formula. This formula is used in Section IV to show the power loss reduction using the minimum filter inductance.


A. Passive LCL Filter

Fig. 2(a) shows the structure of a passive LCL filter. It has an additional filter capacitor when compared with the conventional L filter. A schematic of an LCL filter at a high frequency is shown in Fig. 2(b). The LCL circuit is characterized so that the grid-side current harmonics are reduced by the filter capacitor Cf. However, the resonance caused by the L and C network occurs at the frequency described in (1), which induces the resonance peaks and unstable closed-loop system operation.

그림입니다.
원본 그림의 이름: CLP0000045c0004.bmp
원본 그림의 크기: 가로 396pixel, 세로 237pixel   (1)


Fig. 2. Equivalent models of a passive LCL filter: (a) At line frequency; (b) At a high frequency.

그림입니다.
원본 그림의 이름: CLP0000045c29c1.bmp
원본 그림의 크기: 가로 1380pixel, 세로 447pixel

(a)

그림입니다.
원본 그림의 이름: CLP0000045c0001.bmp
원본 그림의 크기: 가로 1356pixel, 세로 469pixel

(b)


The instability of a closed-loop system can be interpreted by the inverter voltage to the grid-side current transfer function of the LCL filter. In a transfer function without damping resistance, which is described in (2), a second order term in the denominator does not exist. Therefore, the transfer function makes the closed-loop system unstable and is analyzed by the Routh-Hurwitz’s stability criterion [21]. However, in the case of the LCL filter with a damping resistance, which is described in (3), the second order term in the denominator appears and the stability of the closed-loop system can be guaranteed by tuning the damping resistance Rd.

그림입니다.
원본 그림의 이름: CLP0000045c0005.bmp
원본 그림의 크기: 가로 995pixel, 세로 204pixel       (2)

그림입니다.
원본 그림의 이름: CLP0000045c0006.bmp
원본 그림의 크기: 가로 1382pixel, 세로 211pixel          (3)

However, due to the damping resistance, a zero in the numerator can induce performance degradation in high frequency harmonic attenuation. The effectiveness of high frequency harmonic attenuation decreases as the damping resistance increases. In addition, power loss increases as the damping resistance increases. Therefore, a minimum resistance design is required for the filter design. The design of a damping resistance considering both the minimum value and the stability of the closed-loop system is covered in Section III.


B. Current Harmonics at the Grid-side

In Fig. 2(b), the phase voltage harmonics at the inverter side generate current harmonics in the grid side. The voltage harmonics are inevitable factors due to the pulse-width modulation (PWM) by the switching mechanism of the inverter. As shown in Fig. 3(a), those voltage harmonics are generated at each switching frequency. In addition, they also produce grid-side current harmonics at each switching frequency.

IEEE-519 states that grid-side current harmonics over 35th order of the fundamental frequency at a rated power should be attenuated to under 0.3% of the rated current. The highest current harmonics appear at around the fundamental switching frequency. These values should be limited to satisfy the IEEE-519 standard. Conventional studies have presented rough design guides to suppress current harmonics [12]-[18]. These methods make it difficult to tightly match the magnitudes of the current harmonics exactly to 0.3%. Therefore, a mathematical approach is a better solution to systematically design the LCL filter. The magnitude of the current harmonics can be designed by following three steps.


Fig. 3. FFT results of the inverter voltage and grid current (15 kHz): (a) Entire frequency; (b) Around the switching frequency.

그림입니다.
원본 그림의 이름: image8.png
원본 그림의 크기: 가로 1074pixel, 세로 453pixel

(a)

그림입니다.
원본 그림의 이름: image9.png
원본 그림의 크기: 가로 1079pixel, 세로 441pixel

(b)


First, the expression of the phase voltage harmonics should be obtained by a mathematical approach for a precise design. For the sinusoidal PWM method, the phase voltage harmonics can be mathematically expressed by using the double Fourier integral method based on a Bessel function as follows [15]:

그림입니다.
원본 그림의 이름: CLP0000045c0007.bmp
원본 그림의 크기: 가로 1219pixel, 세로 184pixel       (4)

where M is the modulation index at the rated load, Vdc is the dc link voltage, m is the order of the switching frequency, n is the order of the sideband of the fundamental frequency, ωc is the carrier angular frequency, ωo is the fundamental angular frequency, q=m+n(ωo/ωc), and Jn is the Bessel function represented by the integral form. The phase voltage harmonics of other modulation methods, such as the space vector PWM and the discontinuous PWM, are shown in [15].

Second, the transfer function of the LCL filter, represented in (3), is designed by the terms of the filter parameters. This transfer function determines the amount of current injections from the inverter-side voltage to the grid-side current.

Finally, the magnitudes of the current harmonics can be calculated by the product of the transfer function in (3) and the voltage harmonics in (4). Fig. 3(b) shows that the highest current harmonics occur at the double side band of the fundamental switching frequency (m=1, n=-2 and m=1, n=2) and can be expressed as follows:

그림입니다.
원본 그림의 이름: CLP0000045c0008.bmp
원본 그림의 크기: 가로 568pixel, 세로 210pixel     (5)

그림입니다.
원본 그림의 이름: CLP0000045c0009.bmp
원본 그림의 크기: 가로 568pixel, 세로 215pixel     (6)

where V1,-2 and V1,+2 denotes the magnitudes of the phase voltage harmonics at m=1, n=-2 and m=1, n=2, respectively.

As a result, the current harmonics expressed in (5) and (6) should be lower than 0.3% of the rated current. Since the value of (3) becomes smaller as the frequency rises, the current harmonic in (5) has to be a value higher than (6) to be considered.

Fig. 4 shows an example of the filter inductance and capacitance combination for various current harmonics using (5). The red line (0.3%) in Fig. 4 is the threshold for the IEEE-519 standards. The current harmonics can be designed to be 0.1% or 0.2%. However, this increases the size of the filter components. Therefore, the design should be targeted to 0.3% for the minimum size of the filter.


그림입니다.
원본 그림의 이름: image10.png
원본 그림의 크기: 가로 901pixel, 세로 553pixel

Fig. 4. Parameter values according to various current harmonics.


C. Power Loss in an LCL filter

The power losses in an LCL filter are the conduction loss through a winding resistor in the filter inductor and the damping resistor. The winding resistance is the value produced by the winding through the wire to make the inductor. The conduction loss in the winding resistor can be calculated as follows:

그림입니다.
원본 그림의 이름: CLP0000045c000a.bmp
원본 그림의 크기: 가로 695pixel, 세로 120pixel          (7)

where Rg and Ri represent the winding resistor in the grid and in the inverter-side filter inductance, and Iref is the current reference. The winding resistance changes according to the filter inductance. In a solenoid, the inductance is proportional to the square of the turn ratio of the wire as follows:

그림입니다.
원본 그림의 이름: CLP0000045c000b.bmp
원본 그림의 크기: 가로 200pixel, 세로 175pixel   (8)

where 그림입니다.
원본 그림의 이름: CLP0000045c0023.bmp
원본 그림의 크기: 가로 55pixel, 세로 54pixel is the reluctance of the magnetic core used in the filter inductor. Since the winding resistance is proportional to the turn ratio of the wire, the winding resistance increases proportionally to the square root of the filter inductance as follows:

그림입니다.
원본 그림의 이름: CLP0000045c000c.bmp
원본 그림의 크기: 가로 395pixel, 세로 144pixel   (9)

where k is the constant value that defines the other values of the winding resistor. As a result, a higher filter inductance can induce a higher winding resistance to have a higher conduction loss.

The conduction loss in the damping resistor can be calculated separately by the fundamental (60 Hz) and the harmonic current flowing through the damping resistor [15]. The conduction loss is calculated using the voltage and impedance formed in the R-C branch. Assuming the fundamental current in the grid-side is a purely sinusoidal waveform, the voltage at the R-C branch is calculated as follows:

그림입니다.
원본 그림의 이름: CLP0000045c000d.bmp
원본 그림의 크기: 가로 703pixel, 세로 161pixel         (10)

where VR-C is the voltage at the R-C branch, and Vg is the grid voltage. Since the impedance of the damping resistor is a lot smaller than the filter capacitor at the fundamental frequency, the power loss by the fundamental current can be simply shown as follows:

그림입니다.
원본 그림의 이름: CLP0000045c000e.bmp
원본 그림의 크기: 가로 552pixel, 세로 124pixel      (11)

Using the same method as above, the conduction caused by the current harmonic is calculated as shown in (12). For simple calculation, only the dominant current components 그림입니다.
원본 그림의 이름: CLP0000433c4824.bmp
원본 그림의 크기: 가로 509pixel, 세로 69pixel that make up the current harmonic are included in (12).

그림입니다.
원본 그림의 이름: CLP0000045c000f.bmp
원본 그림의 크기: 가로 1019pixel, 세로 271pixel      (12)

The total conduction loss in the damping resistor is the sum of (11) and (12). The conduction loss can be reduced by decreasing the damping resistance and the filter capacitance. A low filter capacitance results in a high impedance in the R-C branch, which induces a small current with a low conduction loss.



Ⅲ. CURRENT CONTROLLER DESIGN

Fig. 5(a) shows the two control loops used in grid connected three-phase inverters. One of the control loops is an outer loop to regulate the output DC voltage, and the other is an inner loop to track the sinusoidal current reference. The inner loop can make the system unstable due to the resonance peaks generated from the L and C network.


Fig. 5. Controller diagram of a 3 phase inverter: (a) Entire system, (b) Inner loop.

그림입니다.
원본 그림의 이름: CLP0000045c0010.bmp
원본 그림의 크기: 가로 1113pixel, 세로 823pixel

(a)

그림입니다.
원본 그림의 이름: CLP0000045c0011.bmp
원본 그림의 크기: 가로 1607pixel, 세로 352pixel

(b)


Fig. 5(b) shows the structure of the inner control loop. This inner loop contains a current controller and a plant function. The transfer function of the plant comes from the LCL filter expressed by (3). To make the closed-loop system stable, the open-loop transfer function in the inner loop should have a positive gain (GM) and phase margin (PM). Since a 180° phase lag occurs at the resonance frequency, the resonance peak should be lower than 0 dB for a positive GM, where the resonance peak can be suppressed by the damping resistor. In addition, the crossover frequency of the open-loop transfer function should be lower than the resonance frequency to avoid a negative PM.

The damping resistance is recommended to be one-third of the impedance of the filter capacitor at the resonant frequency [16]. Since the above method does not consider the current controller design, accurate values of the GM and PM cannot be derived. Therefore, for the current controller, a detail design methodology using specific values for the GM and PM is required.

PI controllers are mostly used for power control applications as current controllers [23]. There are several tuning methods such as Tyreus-Luyben and Ziegler-Nichols [24], as well as the IMC, which is applied in this paper. Using the IMC, accurate values of the GM and PM can be effectively obtained when compared with other tuning methods. The PI coefficients are directly matched to the plant model’s parameters and the desired crossover frequency is easily obtained. As a result, the current controller can be easily derived for the desired GM and PM values.

Fig. 6(a) shows the control system structure of an IMC. It is a design method using the plant model. Due to its unique structure, the IMC can suppress all of the plant dynamics and it can make the output value equal to the input value for all of the time variables. The controller C(s) is expressed by the plant model parameters and the desired crossover frequency. To easily implement it in a PI controller, the IMC structure shown in Fig. 6(a) can be changed into the classical control structure shown in Fig. 6(b). In (13), U(s) is defined as the classical controller. It can be expressed as a product of the first-order low pass filter and an inverse function of the plant model. There are more detail descriptions in [25].


Fig. 6. Block diagram of an internal model controller: (a) IMC structure; (b) Classical control system structure.

그림입니다.
원본 그림의 이름: CLP0000045c0012.bmp
원본 그림의 크기: 가로 1622pixel, 세로 634pixel

(a)

그림입니다.
원본 그림의 이름: CLP0000045c0013.bmp
원본 그림의 크기: 가로 1630pixel, 세로 618pixel

(b)


In the frequency range below the resonant frequency, the LCL filter looks like a simple inductive L filter. Therefore, the IMC can be designed using an L filter for the following two reasons. First, the crossover frequency is designed to be lower than the resonant frequency. Second, the performance of the controller is mainly affected by the characteristics of the operating frequency lower than the crossover frequency. With the L model, the structure of U(s) can be derived as follows:

그림입니다.
원본 그림의 이름: CLP0000045c0014.bmp
원본 그림의 크기: 가로 1344pixel, 세로 205pixel   (13)

where α is the desired cross-over angular frequency.

The structure of U(s) is identical to the structure of a PI controller. As a result, the PI coefficient and the desired crossover frequency are directly designed by the plant model and the variable α respectively.

For the inner loop system stability, a positive GM and PM should be guaranteed. The open-loop transfer function is defined by (14) and the delays of the sampling and PWM signals can be neglected for the sake of a simple calculation.

그림입니다.
원본 그림의 이름: CLP0000045c0015.bmp
원본 그림의 크기: 가로 612pixel, 세로 115pixel    (14)

For a positive GM, the magnitude at the resonance frequency should be lower than 0 dB as follows:

그림입니다.
원본 그림의 이름: CLP0000045c0016.bmp
원본 그림의 크기: 가로 1387pixel, 세로 272pixel (15)

Neglecting small terms such as Ki/ωr, the minimum damping resistance with the desired GM can be obtained as follows:

그림입니다.
원본 그림의 이름: CLP0000045c0017.bmp
원본 그림의 크기: 가로 1147pixel, 세로 292pixel          (16)

where χ represents the desired GM in the dB scale. As a result, the minimum damping resistance guarantees system stability. It also reduces the power loss and performance degradation in the high frequency harmonic attenuation.

For a sufficient PM, the crossover frequency should be considered in the controller design. If the crossover frequency is close to the resonant frequency, the PM can be insufficient due to a 180° phase lag at the resonance frequency. Considering the delays of the sampling and PWM signals, the crossover frequency should be 0.3 times lower than the resonant frequency as follows [26]:

그림입니다.
원본 그림의 이름: CLP0000045c0018.bmp
원본 그림의 크기: 가로 314pixel, 세로 100pixel      (17)

where fc is the crossover frequency, and fr is the resonant frequency.

Fig. 7 shows an example of the open-loop transfer function H(s) to which the IMC is applied. The parameters of the LCL filter and current controller are listed in Table I. Below the resonant frequency, the transfer function of the LCL filter operates like an L filter which guarantees (13). The resonant peak is suppressed to have -3 dB by (16). In addition, the desired crossover frequency is set to 0.1 times the switching frequency to satisfy (17). Therefore, a positive GM and PM are guaranteed using the proposed design to have a stable closed-loop system.


그림입니다.
원본 그림의 이름: image28.png
원본 그림의 크기: 가로 819pixel, 세로 526pixel

Fig. 7. Open-loop transfer function H(s) using the IMC method.


TABLE I PARAMETER OF H(S)

Parameter

Value

Switching frequency

15 kHz

Crossover frequency

1.5 kHz

Resonant frequency

7.1 kHz

Li , Lg

2 mH

Cf

0.5 uF

Rd

9.42 Ω

Ri , Rg

10 mΩ

Kn

37

Ki

188


Fig. 8 shows experiment results with a high crossover frequency. Even if the GM is properly selected by the damping resistor, the system can be unstable when the PM is not guaranteed by the crossover frequency. In this case, the crossover frequency is selected to be higher than 0.3 times the resonant frequency, which can obtain an insufficient PM. For this reason, Fig. 8(a) shows oscillations in the steady state operation, and Fig. 8(b) shows unstable waveforms when a step load is applied. As a result, the current controller should be designed well even if damping resistance exists in the converter.


Fig. 8. Unstable system with a high crossover frequency: (a) Steady state operation at 3.3kW; (b) Step load from 3.3kW to 5kW.

그림입니다.
원본 그림의 이름: image30.png
원본 그림의 크기: 가로 708pixel, 세로 400pixel

(a)

그림입니다.
원본 그림의 이름: image31.png
원본 그림의 크기: 가로 708pixel, 세로 465pixel

(b)



Ⅳ. FILTER DESIGN


A. Filter Design Requirements

When designing an LCL filter, there are several design requirements for the power constraints and system stability [16], [27]. These requirements have to be satisfied before other considerations such as efficiency and size. The filter design requirements are as follows:

1) The resonant frequency of the LCL filter should be limited for system stability. For the lower boundary, the resonant frequency should be higher than the crossover frequency. Because of the 180° phase lag at the resonance frequency as well as the delays of the sampling and pulse width modulation, the PM cannot be sufficient at the crossover frequency. To avoid this problem, the resonant frequency should be 0.3 times higher than the crossover frequency as shown in (17). For the upper boundary, the resonant frequency should be lower than the Nyquist frequency described as follows [16]:

그림입니다.
원본 그림의 이름: CLP0000045c0019.bmp
원본 그림의 크기: 가로 297pixel, 세로 93pixel       (18)

  where fs is the switching frequency.

2) Using a phase diagram in the steady state, the minimum output DC voltage is related to the total filter inductance as follows [27]:

그림입니다.
원본 그림의 이름: CLP0000045c001a.bmp
원본 그림의 크기: 가로 971pixel, 세로 150pixel        (19)

  where VLN is the line to neutral grid voltage. With the desired output DC voltage and the rated current, the maximum filter inductance can be derived from (19) as follows:

그림입니다.
원본 그림의 이름: CLP0000045c001b.bmp
원본 그림의 크기: 가로 541pixel, 세로 320pixel       (20)

3) The reactive power by the filter capacitor should be lower than 5% of the rated power as shown in (21) [16].

그림입니다.
원본 그림의 이름: CLP0000045c001c.bmp
원본 그림의 크기: 가로 463pixel, 세로 204pixel          (21)


B. Proposed Mathematical Design Solution

When compared to existing design methods [12]-[18], the proposed mathematical design solution is presented to directly find the values of the filter parameters that suppress high frequency current harmonics to 0.3%. Furthermore, a minimum filter inductance can be obtained, which can reduce the size of the filter. Since the inductor is made up of magnetic cores, the filter inductor is more serious in terms of its cost and size than the filter capacitor. Reducing the inductance is the preferred method to decrease the total cost and filter size. The mathematical design solution is shown in the following steps based on the design methods from Section II and III. The following steps are carried out under the condition listed in Table II.


TABLE II PARAMETER OF A THREE-PHASE INVERTER SYSTEM

Parameter

Value

Grid Voltage

220V

Grid Frequency

60Hz

DC-Link Voltage

380V

Switching Frequency

15kHz

Output Power

5kW


1) By applying the IMC in the current controller, the minimum damping resistance can be mathematically derived using (16) to ensure closed-loop system stability. The GM is set to 3 dB and the crossover frequency is set to 0.1 times the switching frequency for smooth control [28]. The minimum damping resistance can be calculated as follows:

그림입니다.
원본 그림의 이름: CLP0000045c001d.bmp
원본 그림의 크기: 가로 1289pixel, 세로 287pixel          (22)

2) Under the sinusoidal PWM method, the filter inductance and capacitance should satisfy the grid-side current harmonics with 0.3% as follows:

그림입니다.
원본 그림의 이름: CLP0000045c001e.bmp
원본 그림의 크기: 가로 745pixel, 세로 221pixel           (23)

By substituting (22) into (23), the obtained filter inductance and capacitance makes the grid-side current harmonics as 0.3%. It also guarantees system stability with the minimum damping resistance. The filter inductance ratio between the grid side and the inverter side is one to one because of its simple calculation and stability reasons [17].

3) The selected filter inductance and capacitance from the above procedure can be drawn as the dotted red line in Fig. 9(a). In the upper region of the dotted red line, the grid-side current harmonics are lower than 0.3%, and vice versa.

4) Finally, lines are drawn with circle markers that limit the filter inductance and capacitance. The lines are the previous design requirements from (17), (18), (20) and (21). The minimum filter inductance can be obtained under the above conditions.

Fig. 9(b) shows the filter inductance and capacitance from the mathematical design methodology. In this system, the design requirements from (20) and (21) limit the filter inductance and capacitance as 9 mH and 6.8 uF, respectively. The other design requirements from (17) and (18) are illustrated in Fig. 9(b), where the dotted red line represents the minimum and maximum filter inductances. By numerically solving the above analysis, the minimum and maximum filter inductances can be obtained as follows:

그림입니다.
원본 그림의 이름: CLP0000045c001f.bmp
원본 그림의 크기: 가로 1405pixel, 세로 170pixel      (24)

그림입니다.
원본 그림의 이름: CLP0000045c0020.bmp
원본 그림의 크기: 가로 992pixel, 세로 199pixel    (25)

The obtained minimum and maximum filter inductance are illustrated in Y1 (L=0.9 mH, C=2.24 uF) and Y2 (L=1.81 mH, C=0.48 uF) in Fig. 9(b). The minimum filter inductance is limited by (17), which guarantees a sufficient PM. The maximum filter inductance is limited by (18) to have a resonant frequency lower than the Nyquist frequency.


Fig. 9. Filter L and C of the proposed design methodology: (a) Satisfying the grid-side current harmonic as 0.3%; (b) Final design including the design requirements.

그림입니다.
원본 그림의 이름: image40.png
원본 그림의 크기: 가로 720pixel, 세로 422pixel

(a)

그림입니다.
원본 그림의 이름: image41.png
원본 그림의 크기: 가로 720pixel, 세로 415pixel

(b)


C. Power Loss Analysis in an LCL Filter

The power loss at the rated power is analyzed for the filter inductance and capacitance satisfying 0.3%, which is obtained in the above procedure. The power loss is shown in Fig. 10, where the red line shows the power loss at the 0.3% harmonic limitation.

The damping resistance is calculated as 5.7 Ω in the Y1 design and as 11.9 Ω in the Y2 design. Since the filter capacitance becomes smaller as the filter inductance increases, a high impedance is formed in the R-C branch. The power loss in the damping resistor decreases as the filter inductance increases. As a result, the minimum power loss is 2.7 W at the maximum filter inductance (Y2), and the maximum power loss is 3.9 W at the minimum filter inductance (Y1). They are both shown in Fig. 10(a).


Fig. 10. Power losses in an LCL filter: (a) Damping resistance loss; (b) Total power loss including the winding resistance loss.

그림입니다.
원본 그림의 이름: CLP0000045c0021.bmp
원본 그림의 크기: 가로 1427pixel, 세로 842pixel

(a)

그림입니다.
원본 그림의 이름: CLP0000045c0022.bmp
원본 그림의 크기: 가로 1413pixel, 세로 840pixel

(b)


However, because of the winding resistance of the filter inductor, the total power loss increases as the filter inductance increases. The winding resistance is calculated as 40 mΩ in the Y1 design and as 56.5 mΩ in the Y2 design. The other remaining winding resistances are calculated by (9). Since the power loss due to the winding resistance is relatively higher than the power loss due to the damping resistance, the total power loss reaches its maximum at the maximum filter inductance (Y2) of 21.86 W. In addition, the total power loss is minimized at the minimum filter inductance (Y1) of 17.5 W. These results are shown in Fig. 10(b).

As a result, the minimum power dissipation in the damping resistor appears at the maximum inductance with the minimum capacitance. However, due to the winding resistance, the minimum total power loss can be obtained at the minimum inductance with the minimum winding resistance.


D. Performance Analysis

In Fig. 11, a bode plot of G(s) graphically shows how the high attenuation performances at the left double side band of the switching frequency (15 kHz) can be the same as each other even though they have different filter inductor values (Y1 and Y2). At first, the higher inductance has a better high frequency attenuation performance. However, the resonant frequency decreases as the filter capacitance increases and it shifts the slope of the transfer function G(s) more quickly from -20 dB/decade to -40 dB/decade. Therefore, even though the filter inductances are different from each other, the mathematical analysis in (5) can be used to adjust the filter capacitance to obtain the same high frequency attenuation performance at the desired operating frequency. At the second harmonics of the switching frequency (30 kHz), the higher inductance in the Y2 design exhibits better attenuation performance. Since the current harmonics at the second harmonics of the switching frequency are much smaller than the values at the fundamental switching frequency, this attenuation performance is not considered for the IEEE-519 standards.


그림입니다.
원본 그림의 이름: image44.png
원본 그림의 크기: 가로 801pixel, 세로 576pixel

Fig. 11. Bode plot of G(s) with respect to filter inductance.



Ⅴ. EXPERIMENT RESULTS

The mathematical solution from Section IV is verified with a 5-kW prototype grid-connected three-phase inverter. The circuit configuration is shown in Fig. 12. A digital signal processor (TMS320f28335) is used to regulate the grid-side current and output DC voltage. The parameters of the Y1 and Y2 designs are chosen to show the validity of the proposed design. The design candidate of Y1 represents the targeted minimum filter inductance and the design of Y2 represents the conventional filter parameters with a large enough inductance. These two cases show that the Y2 filter inductance can be reduced to the Y1 filter inductance for obtaining the same current harmonic level limited to 0.3%. In addition, the power loss is reduced in the Y1 design. These results are summarized in Tables III and IV.


그림입니다.
원본 그림의 이름: image45.jpeg
원본 그림의 크기: 가로 478pixel, 세로 450pixel

Fig. 12. 5-kW prototype three-phase inverter.


TABLE III EXPERIMENT RESULTS OF Y1 AND Y2

Li` Lg

Cf

Rd

I1, -2/Iref

0.93mH

2.29uF

6Ω

0.289%

1.87mH

0.47uF

12Ω

0.286%


TABLE IV POWER LOSSES OF Y1 AND Y2

 

Rwinding

Pdaming

Pwinding

Ptotal

Y1

40mΩ

4.5W

13.69W

18.19W

Y2

58mΩ

2.88W

19.85W

22.73W


The current controllers of Y1 and Y2 are designed by considering the minimum damping resistor. Fig. 13 shows stable operation under step load changes, where the DC output voltage and the three-phase currents of Y1 and Y2 do not diverge. As shown in Fig. 14, which is a smaller time scale from Fig. 13, the three-phase currents are stabilized without oscillations when the load changes.


Fig. 13. Experimental results of step-load changes: (a) Y1 (L=0.93 mH, C=2.29 uF); (b) Y2 (L=1.87 mH, C=0.47 uF).

그림입니다.
원본 그림의 이름: image46.jpeg
원본 그림의 크기: 가로 719pixel, 세로 348pixel

(a)

그림입니다.
원본 그림의 이름: image47.jpeg
원본 그림의 크기: 가로 720pixel, 세로 349pixel

(b)


그림입니다.
원본 그림의 이름: image48.png
원본 그림의 크기: 가로 718pixel, 세로 348pixel

Fig. 14. Experimental results of step-load change with a smaller time scale (3.3 kW to 5 kW, Y1).


Fig. 15 shows the steady state of Y1 and Y2 under the rated 5 kW, and the design of Y2 has lower current ripples at the inverter-side due to the high filter inductance. However, due to the high filter capacitance in the Y1 design, both the Y1 and Y2 designs have nearly the same current ripples at the grid-side.


Fig. 15. Experimental results of steady-state waveforms under the rated 5 kW: (a) Y1 (L=0.93 mH, C=2.29 uF), (b) Y2 (L=1.87 mH, C=0.47 uF).

그림입니다.
원본 그림의 이름: image49.png
원본 그림의 크기: 가로 707pixel, 세로 410pixel

(a)

그림입니다.
원본 그림의 이름: image50.png
원본 그림의 크기: 가로 709pixel, 세로 416pixel

(b)


In Fig. 16, the frequency spectrum results of the Y1 and Y2 designs shows that the grid-side current ripples are nearly the same with the current harmonics of I1,-2 /Iref as 0.289% and 0.286%, respectively. These values tightly satisfy the IEEE-519 standards. The Y2 design has lower current harmonics at the second switching frequency due to the inductance difference, as shown in Fig. 6. As a result, the Y1 design has the minimum filter inductance, which is twice as small as the inductance of Y2, while satisfying the IEEE-519 standards.


Fig. 16. Frequency spectrum results: (a) Y1 (L=0.93 mH, C=2.29 uF), (b) Y2 (L=1.87 mH, C=0.47 uF).

그림입니다.
원본 그림의 이름: image51.png
원본 그림의 크기: 가로 718pixel, 세로 406pixel

(a)

그림입니다.
원본 그림의 이름: image52.png
원본 그림의 크기: 가로 725pixel, 세로 396pixel

(b)


Table IV shows the power loss at the rated power in the LCL filter according to the designs of Y1 and Y2. Similar to the simulation results shown in Fig. 9, the power loss in the damping resistance is higher in the Y1 design at 4.5 W than that in the Y2 design at 2.88 W. Since the winding resistance of the Y1 design is 40 mΩ, which is lower than that of the Y1 design at 58 mΩ, the total power loss decreases in the Y1 design to 18.19 W, which is lower than that of the Y2 design at 22.73 W.



Ⅵ. CONCLUSIONS

This paper proposed the mathematical design solution for the passive LCL filter to directly derive optimal filter parameters that can suppress high frequency current harmonics limited to 0.3%. Using this solution, the filter parameters can be minimized to satisfy the IEEE-519 regulation up to 0.3%. In addition, the minimum filter inductance is mathematically derived, which can reduce the size of the filter. The power loss in the LCL filter can be decreased by using the minimum inductance. Furthermore, a stable current controller can be designed using the minimum damping resistance that is mathematically derived to obtain a lower power loss, less performance degradation in terms of the high frequency harmonic attenuation, and enough gain and phase margins of the current controller, which can guarantee the stable operation of the closed-loop system. Finally, experimental results verify both the effectiveness of the proposed solution and the stable current controller design using the minimum damping resistance.



ACKNOWLEDGMENT

This research was supported by the KEPCO under the project entitled by “Demonstration Study for Low Voltage Direct Current Distribution Network in an Island.” (No. D3080).



REFERENCES

[1] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std. 519-1992, May 10, 1992.

[2] M. A. Elsaharty and H. A. Ashour, “Passive L and LCL filter design method for grid-connected inverters,” in Proc. IEEE Innovative Smart Grid Technol., pp. 13-18, 2014.

[3] J. Dannehl, M. Liserre, and F. W. Fuchs, “Filter-based active damping of voltage source converters with LCL filter,” IEEE Trans. Ind. Electron., Vol. 58, No. 8, pp. 3623-3633, Aug. 2011.

[4] G. Shen, X. Zhu, J. Zhang, and D. Xu, “A new feedback method for PR current control of LCL-filter-based grid- connected inverter,” IEEE Trans. Ind. Electron., Vol. 57, No. 6, pp. 2033-2041, Jun. 2010.

[5] J. R. Massing, M. Stefanello, H. A. Grundling, and H. Pinheiro, “Adaptive current control for grid-connected converters with LCL filter,” IEEE Trans. Ind. Electron., Vol. 59, No. 12, pp. 4681-4693, Dec. 2012.

[6] K. Jalili and S. Bernet, “Design of LCL filters of active- front-end two level voltage source converters,” IEEE Trans. Ind. Electron., Vol. 56, No. 5, pp. 1674-1689, May 2009.

[7] W. Wu, Y. He, and F. Blaabjerg, “An LLCL power filter for single-phase grid-tied inverter,” IEEE Trans. Power Electron., Vol. 27, No. 2, pp. 782-789, Feb. 2012.

[8] J. Fang, G. Xiao, X. Yang, and Y. Tang, “Parameter design of a novel series parallel-resonant LCL filter for single- phase half-bridge active power filters,” IEEE Trans. Power Electron., Vol. 32, No. 1, pp. 200-217, Jan. 2017.

[9] X.Wang, X. F. Blaabjerg, and P. C. Loh, “Grid-current- feedback active damping for LCL resonance in grid- connected voltage source inverters,” IEEE Trans. Power Electron., Vol. 3, No. 1, pp. 213-223, Jan. 2016

[10] W. Yao, Y. Yang, X. Zhang, F. Blaabjerg, and P. C. Loh, “Design and analysis of robust active damping for LCL filters using digital notch filters,” IEEE Trans. Power Electron., Vol. 32, No. 3, pp, 2360-2375, Mar. 2017.

[11] R. Peña-Alzola, M. Liserre, F. Blaabjerg and T. Kerekes, “Self-commissioning notch filter for active damping in three phase LCL-filter based grid converters,” 2013 15th European Conference on Power Electronics and Applications (EPE), pp. 1-9, 2013.

[12] K. H. Ahmed, S. J. Finney, and B. W. Williams, “Passive filter design for three-phase inverter interfacing in distributed generation,” in Proc. Compat. Power Electron. Conf., pp. 1-9, 2007.

[13] M. T. Bina and E. Pashajavid, “An efficient procedure to design passive LCL-filters for active power filters,” Elect. Power Syst. Res., Vol. 79, No. 4, pp. 606-614, Apr. 2009.

[14] W. Wu, Y. He, T. Tang, and F. Blaabjerg, “A new design method for the passive damped LCL and LLCL filter-based single-phase grid-tied inverter,” IEEE Trans. Ind. Electron., Vol. 60, No. 10, pp. 4339-4350, Oct. 2013.

[15] R. Pe˜na-Alzola, M. Liserre, F. Blaabjerg, R. Sebasti´an, J. Dannehl, and F. W. Fuchs, “Analysis of the passive damping losses in LCL-filter-based grid converters” IEEE Trans. Power Electron., Vol. 28, No. 6, pp. 2642-2646, Jun. 2013.

[16] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL filter-based three-phase active rectifier,” IEEE Trans. Ind. Appl., Vol. 41, No. 5, pp. 1281-1291, Sep./Oct. 2005.

[17] M. Liserre, F. Blaabjerg, and A. Dell’Aquila, “Step-by-step design procedure for a grid-connected three-phase PWM voltage source converter,” Int. J. Electron., Vol. 91, No. 8, pp. 445-460, Aug. 2004.

[18] R. Beres, X. Wang, F. Blaabjerg, M. Liserre, and C. L. Bak, “A review of passive power filters for three-phase grid- connected voltage source inverters,” IEEE Trans. Power Electron., Vol. 4, No. 1, pp. 54-69, Mar. 2016.

[19] Y. Liu, W. Wu, Y. He, Z. Lin, F. Blaabjerg, and H. Chung, “An efficient and robust hybrid damper for LCL or LLCL based grid-tied inverter with strong grid-side harmonic voltage effect rejection,” IEEE Trans. Ind. Electron., Vol. 63, No. 2, pp. 926-936, Feb. 2016.

[20] Y. Lei, W. Xu, C. Mu, Z. Zhao, H. Li, and Z. Li, “New hybrid damping strategy for grid-connected photovoltaic inverter with LCL filter,” IEEE Trans. Appl. Superconduct., Vol. 24, No. 5, Oct. 2014.

[21] V. Krishnamurthi, “Implications of Routh stability criteria,” IEEE Trans. Autom. Contr., Vol. ac-25, No. 3, pp. 554-555, Jun. 1980.

[22] D. G. Holmes and T. A. Lipo, Pulse Width Modulation for Power Converters: Principles and Practice, New York, NY, USA:Wiley-IEEE Press, 2003.

[23] M. P. Kazmierkowski and L. Malesani, “Current control techniques for three-phase voltage-source PWM converters: A survey,” IEEE Trans. Ind. Electron., Vol. 45, No. 5, pp. 691-703, Oct. 1998

[24] P. Cominos and N. Munro, “PID controllers: recent tuning methods and design to specification,” lEE Proceedings- Control Theory and Applications, Vol. 149, No. 1, pp. 46-53, Jan. 2002.

[25] C. E. Garcia and M. Morari, “Internal model control. 1. A unifying review and some new results,” Ind. Eng. Chemistry Process Design Development, Vol. 21, No. 2, pp. 308-323, Apr. 1982.

[26] Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, “Generalized design of high performance shunt active power filter with output LCL filter,” IEEE Trans. Ind. Electron., Vol. 59, No. 3, pp. 1443–1452, Mar. 2012.

[27] M. Kazmierkowski, R. Krishnan, and F. Blaabjerg, Control in Power Electronics—Selected Problems. New York: Academic, 2002.

[28] R. Ottersten, “On control of back-to-back converters and sensorless induction machine drives,” Ph.D. dissertation, Chalmers Univ. Technol., Gothenburg, Sweden, 2003.



그림입니다.
원본 그림의 이름: image55.jpeg
원본 그림의 크기: 가로 190pixel, 세로 225pixel

Jun-Young Lee received his B.S. degree in Electrical Engineering from Sogang University, Seoul, Korea, in 2016. He is presently working towards his Ph.D. degree in School of Electrical Engineering, Ulsan National Institute of Science and Technology (UNIST), Ulsan, Korea. His current research interests include low-voltage dc distribution systems, and bi-directional AC-DC and DC-DC converters.


그림입니다.
원본 그림의 이름: image56.jpeg
원본 그림의 크기: 가로 239pixel, 세로 336pixel

Young-Pyo Cho received his B.S. and M.S. degrees in Electrical Engineering from Korea University, Korea, in 2009 and 2012, respectively. He is a researcher of the KEPCO Research Institute from 2015.


그림입니다.
원본 그림의 이름: image53.jpeg
원본 그림의 크기: 가로 190pixel, 세로 225pixel

Ho-Sung Kim received the B.S., M.S. and Ph.D. degrees in electrical engineering from Pusan National University, Busan, Korea, in 2007, 2009, and 2013, respectively. Since 2007, he has been a Senior Researcher with the Power Conversion Research Center, KERI, Changwon, Korea. His main research interests include high-power-density dc–dc converters, high-efficiency bidirectional ac-dc rectifier systems for low-voltage dc distribution, high-efficiency power factor correction circuits, and power converters for solid-state transformers.


그림입니다.
원본 그림의 이름: image54.jpeg
원본 그림의 크기: 가로 190pixel, 세로 225pixel

Jee-Hoon Jung was born in Suwon, Korea, in 1977. He received his B.S., M.S. and Ph.D. degrees from the Pohang University of Science and Technology (POSTECH), Pohang, Korea, in 2000, 2002 and 2006, respectively. From 2006 to 2009, he was a Senior Research Engineer in the Digital Printing Division, Samsung Electronics Co. Ltd., Suwon, Korea. From 2009 to 2010, he was a Postdoctoral Research Associate in the Department of Electrical and Computer Engineering, Texas A&M University of Qatar (TAMUQ), Doha, Qatar. From 2011 to 2012, he was a Senior Researcher in the Power Conversion & Control Research Center, Korea Electrotechnology Research Institute (KERI), Changwon, Korea. Since 2013, he has been a Faculty Member in the School of Electrical and Computer Engineering, Ulsan National Institute of Science and Technology (UNIST), Ulsan, Korea, where he is presently working as an Associate Professor. His current research interests include DC-DC converters, switched-mode power supplies, power control algorithms, high density power conversion using wide band-gap devices, wireless power transfer , and real-time and power HIL simulations of smart grid systems and renewable energy sources. He has been a senior member of the IEEE Power Electronics Society, the IEEE Industrial Electronics Society, the IEEE Power & Energy Society, and the IEEE Industry Application Society. He is a board member of the Korean Institute of Power Electronics (KIPE).