사각형입니다.

https://doi.org/10.6113/JPE.2019.19.5.1303

ISSN(Print): 1598-2092 / ISSN(Online): 2093-4718



Study of Harmonic Suppression of Ship Electric Propulsion Systems


Yifei Wang†,**, Youxin Yuan*, and Jing Chen*


†,*School of Automation, Wuhan University of Technology, Wuhan, China

**University of Wisconsin-Madison, Madison, WI, USA



Abstract

This paper studies the harmonic characteristics of ship electric propulsion systems and their treatment methods. It also adopts effective measures to suppress and prevent ship power systems from affecting ship operation due to the serious damage caused by harmonics. Firstly, the harmonic characteristics of a ship electric propulsion system are reviewed and discussed. Secondly, aiming at problems such as resonant frequency and filter characteristics variations, resonance point migration, and unstable filtering performances in conventional passive filters, a method for fully tuning of a passive dynamic tunable filter (PDTF) is proposed to realize harmonic suppression. Thirdly, to address the problems of the uncontrollable inductance L of traditional air gap iron core reactors and the harmonics of power electronic impedance converters (PEICs), this paper proposes an electromagnetic coupling reactor with impedance transformation and harmonic suppression characteristics (ECRITHS), with the internal filter (IF) designed to suppress the harmonics generated by PEICs. The ECRITHS is characterized by both harmonic suppression and impedance change. Fourthly, the ECRITHS is investigated. This investigation includes the harmonic suppression characteristics and impedance transformation characteristics of the ECRITHS at the fundamental frequency, which shows the good performance of the ECRITHS. Simulation and experimental evaluations of the PDTF are carried out. Multiple PDTFs can be configured to realize multi-order simultaneous dynamic filtering, and can effectively eliminate the current harmonics of ship electric propulsion systems. This is done to reduce the total harmonic distortion (THD) of the supply currents to well below the 5% limit imposed by the IEEE-519 standard. The PDTF also can eliminate harmonic currents in different geographic places by using a low voltage distribution system. Finally, a detailed discussion is presented, with challenges and future implications discussed. The research results are intended to effectively eliminate the harmonics of ship electric power propulsion systems and to improve the power quality of ship power systems. This is of theoretical and practical significance for improving the power quality and power savings of ship power systems.


Key words: Dynamic tuning, Harmonic suppression, Power filter


Manuscript received Mar. 6, 2019; accepted Apr. 19, 2019

Recommended for publication by Associate Editor Xiaoqiang Guo.

Corresponding Author: wyfnhsz88@163.com  Tel: +86-13871397505, Wuhan University of Technology

*School of Automation, Wuhan University of Technology, China

**University of Wisconsin-Madison, USA



I. INTRODUCTION

With the development of power electronics technology, variable frequency speed control technology, pod technology and digital technology based on microprocessors, ship electric propulsion systems have become strong competitors of diesel engines that directly drive the propeller propulsion system with their inherent advantages (such as maneuverability, reliability, and propulsion efficiency). Large-capacity power electronic devices are often employed in ship electric propulsion systems (such as rectification and inverter equipment). All power electronic devices generate a large amount of harmonics during power conversion and control, during which the propulsion is promoted and a large amount of power harmonics are injected into the grid [1], [2]. When a ship electric propulsion system is operating under different conditions, the harmonic content and waveform changes of the ship power system are different [3], [4]. Propulsion inverters serves as the main harmonic source of ship electric propulsion systems [5]. Harmonic content is increasing year by year [6], [7].

The fundamental power created by a generator is converted into the fundamental power flowing to the linear load and fundamental power flowing to the nonlinear load. At the same time, the nonlinear load flows through part of its own fundamental power for absorption, with the other part being converted into harmonic power, which then flows to the system and linear load, and is then converted into heat energy, resulting in an increase in both the equipment capacity and circuit loss, a shortened life of electrical equipment, increasing energy loss of the power grid, and the possibility of resonance of the power system [8]. Harmonics can cause serious interference in communication and electronic equipment, which can result in a potential safety hazard, and problems in terms of the high quality and economic operation of a ship power system. Severe accidents caused by harmonics have occurred at home and abroad [9], [10]. Therefore, the harmonic problems in ship electric propulsion systems must be taken seriously. It is necessary to study these harmonics and their treatment methods, and to adopt effective measures to suppress and prevent ship power systems from affecting ship operation due to the serious damage caused by harmonics. The issue on how to effectively control harmonics below the 5% limit imposed by the IEEE-519 standard [11] while meeting the requirements of safe operation is an important and practical topic in the frontiers of scientific and technological workers.

A large number of experts and scholars at home and abroad have conducted in-depth research on harmonic suppression. The best way to solve the harmonic problem is to install a power filter at the nearest point to the harmonic source. There are three main methods depending on the class of filters: passive power filters (PPFs), active power filters (APFs), and hybrid power filters (HAPFs), which have their own strengths and weaknesses that make them suitable for different occasions, as shown in Table I. In short, these three power filters have their own advantages and disadvantages, which make them suitable for different occasions [12]-[25].A lot of attention has been paid to developing a novel power filter, whose performance is basically the same as that of an active filter, while having a price advantage over the PDTF [10].


TABLE I STRENGTHS AND WEAKNESSES OF DIFFERENT POWER FILTERS

Power filter

References

Strengths

Weaknesses

PPF

[12]-[15]

Simple structure

Large capacity

Low cost

Stable performance

Large storage element

Parallel resonances

Not real time

Greatly affected by the capacitor components

APF

[16]-[19]

High responsiveness

High controllability

Large capacity

Complex control system

Expensive price

High operating conditions

HAPFs

[20]-[24]

High efficiency

Large capacity

High controllability

High reliability

Complex control algorithm

High operating conditions

Expensive price

Height limitation of device


Existing studies on the harmonic suppressing technology of ship power systems focus mainly on harmonic characteristics, suppression research and the influence of converters on the current harmonics of ship power grids, which does not involve multi-order current harmonic suppression. Therefore, based on the study of the harmonic characteristics of a ship power system, an analysis is conducted in this paper from the perspective of PPF. This study focuses on the fact that the L/C parameters of PPF cannot be adjusted, and the poor filtering effect. Therefore, this paper puts forward an ECRITHS, which can optimize PDTFs, with the following organization. The harmonic characteristics of a ship electric propulsion system are reviewed and discussed in Section II. Section III proposes a method for fully tuning a PDTF. The harmonic suppression principle of the PDTF is analyzed in Section IV. The impedance transformation and harmonic suppression characteristics of the ECRITHS are studied in Section V. Simulation and experimental evaluations of a PDTF used for the harmonic suppression of a ship electric propulsion system are presented in Section VI. Section VII gives a detailed discussion and future research directions.



II. HARMONIC CHARACTERISTICS OF A SHIP ELECTRIC PROPULSION SYSTEM

A ship power system, working as a whole, consists of power supply devices, power distribution devices, power grids and loads connected in a certain way. It is a general term for all shipboard devices and networks such as ship energy generation, transmission, distribution and consumption. A typical ship electric propulsion system is shown in Fig. 1.


그림입니다.
원본 그림의 이름: CLP00000f142fef.bmp
원본 그림의 크기: 가로 932pixel, 세로 864pixel

Fig. 1. Composition block diagram of a typical ship electric propulsion system.


In an electric propulsion ship power grid, there are three sources of harmonics. The first source is the harmonics generated by power generation. The second is the harmonics generated by the transmission and distribution systems. The third is the harmonics generated by electrical equipment. The harmonics mentioned above, which are generated by the supply and transmission of power and distribution systems, are designed with harmonic suppression in mind. In addition, the provided power supply can meet the power quality requirements of the electrical equipment. Therefore, this paper takes the harmonics generated by electrical equipment as its research object. The propulsion inverter is the main piece of electrical equipment and also the main harmonic source for a ship electric propulsion system.

The frequency of the harmonic current generated by the propulsion inverter with the n-pulse rectifier circuit is:

그림입니다.
원본 그림의 이름: CLP00000f140001.bmp
원본 그림의 크기: 가로 392pixel, 세로 90pixel, k=1, 2, …           (1)

where f1 is the fundamental frequency of 50Hz. For a propulsion inverter load with a 6-pulse rectifier circuit, the harmonic currents are of the 5th, 7th, 11th and 13th order. Therefore, four PDTFs (5th, 7th, 11th and 13th), which are connected in parallel with two harmonic sources, effectively eliminate the current harmonics of the ship electric propulsion system.



III. METHOD FOR FULLY TUNING OF A PDTF

Aiming at problems such as variations of the resonant frequency and filter characteristics, resonance point migration, and unstable filtering performances in conventional passive filters, a method for fully tuning of a PDTF is proposed. A method for the dynamic tuning of a PDTF is a key technology for the harmonic suppression of ship electric propulsion systems. The main research contents include: the topological structure, the control principle of a PDTFs, and a full tuning method based on the fundamental equivalent impedance and harmonic impedance.


A. Topological Structure of a PDTF

The core component of the PDTF is an ECRITHS. The primary reactance winding of the ECRITHS is connected in series with a filter capacitor group (FCG), the secondary control winding is connected a PEIC, and the secondary filter winding is connected with an IF designed to suppress the harmonics generated by the PEIC. Taking a single PDTF as an example, a block diagram is shown in Fig. 2.


그림입니다.
원본 그림의 이름: CLP00000f140002.bmp
원본 그림의 크기: 가로 721pixel, 세로 754pixel

Fig. 2. Block diagram of a PDTF.


In Fig. 2, Q01 is a circuit breaker, FS1~n is a fuse, KM1~n is a capacitor contactor, Cs is the equivalent capacitance of the FCG, Ls is the equivalent inductance of the primary reactance winding of the ECRITHS, and Ls and Cs constitute the resonant branch of the PDTF. In addition, NL is the harmonic source. The mechanism and control structure of the PDTF have been shown in [25]-[29].

The systematic control structure consists of a main circuit and a control system.The main circuit is mainly composed of Q01, ECRITHS, FCG, KM0, KM1~n and FS1~n. Among these, the ECRITHS is made up of a PEIC and an IF. The PEIC is a three-phase high impedance inverter that is constituted by six thyristors V1~V6 (V1, V3 and V5 are connected at the cathode, while V4, V6 and V2 are connected at the anode) and the reactance control winding of the PEIC. The thyristors are driven through phase control. According to the control principle of power electronic conversion technology, A-B, A-C, B-C, B-A, C-A and C-B correspond to thyristors V1, V3, V5, V4, V6 and V2, respectively. A pair of thyristors is triggered every 60 degrees to realize the impedance transformation of the three-phase high impedance inverter.

The control system consists of a harmonic sensor (SP), a controller, a thyristor pulse trigger board (PTB), a touch screen (TS), a D/A converter (D/A), a digital input and output (I/O), etc.

The control system collects information of the harmonics via the SP and makes control decisions such as data processing and filtering algorithm optimization via the controller. The results are output in two ways. One output is D/A, which controls the PEIC through the PTB, which realizes the transformation and continuous control of the electromagnetic parameters of the ECRITHS. The other output is I/O, which controls the dynamic switching of the FCG of the main circuit. The controller controls the signals output via these two ways to realize the tuning and filtering of harmonics.


B. Control Principle of the PDTF

According to the direction of the harmonic current in a power system, the detuning degree can be expressed by the harmonic current offset. In a power system, part of the harmonic current generated by a nonlinear load enters the filter branch, and part of it enters the grid side. When a PDTF works normally, it resonates at the harmonic frequency, which forms a low impedance bypass to the sub-harmonic current, at which most of the harmonic current is absorbed by the PDTF. When the PDTF mistunes, the resonant frequency of its LsCs series circuit deviates from the harmonic frequency, and the PDTF electrically operates on the sub-harmonic current. When the tuning impedance of the current increases, the harmonic current generated by the load side flows into the power grid in large quantities. This reduces the harmonic current in the filter branch.

Set the hth harmonic current offset ΔIh:

그림입니다.
원본 그림의 이름: CLP00000f140003.bmp
원본 그림의 크기: 가로 435pixel, 세로 96pixel            (2)

where Inf is the effective value of the hth harmonic current of the PDTF branch, Inl is the effective value of the hth harmonic current of the NL. The detuning degree of the PDTF is described by the offset ∆Ih. When the filter is in resonance, the value of ∆Ih is close to 0. However, when the filter is detuning, the harmonic current offset ∆Ih increases, and the detuning degree also increases.

By synchronous sampling of the PDTF branch current If and load current Il, the hth harmonic current Ihf of the PDTF branch and the hth harmonic current Ihl of the load are obtained. With the ∆Ih minimum as the control target, the controller controls the firing angle α of the thyristors in the PEIC.

At the fundamental frequency, the PDTF is mainly used to compensate the reactive power of the system. The capacitor can be input and removed dynamically and timely. Therefore, the overall capacitance reactance can be adjusted. In this way, the capacitor can be put into the system according to the actual needs, and the inductance of the ECRITHS can be adjusted. The PDTF can compensate the reactive power of the system without overcompensation.

At harmonic frequencies, the PDTF is mainly used to absorb harmonics. When the PDTF is in resonance, the controller keeps the firing angle α of the thyristors in the PEIC. When the capacity of the capacitor bank changes, for example, when the temperature changes and time passes, the capacity of the capacitor bank becomes smaller. If the inductance Ls remains unchanged, the actual resonance frequency fh (such as f5 = 250Hz, that is, the 5th harmonic resonance frequency) increases, and the filtering effect is greatly affected. However, the PDTF improves this situation. When the capacitor bank capacity changes, the controller adjusts the firing angle α of the thyristors in the PEIC, and the inductance Ls produced by the primary reactance winding changes. Thus, the inductance Ls of the ECRITHS can be dynamically adjusted so the product of LsCs remains unchanged and the filtering frequency fh remains unchanged. As a result, the filtering accuracy and filtering effect are unaffected.


C. Full Tuning Method based on Fundamental Impedance and Harmonic Impedance

A schematic diagram of the connection between the PDTF and the NL is shown in Fig. 3.


그림입니다.
원본 그림의 이름: CLP00000f140004.bmp
원본 그림의 크기: 가로 782pixel, 세로 309pixel

Fig. 3. Schematic diagram of the PDTF and NL connection.


As shown in Fig. 3, both the NL and the PDTF are connected to the secondary side of the power transformer. Therefore, an equivalent diagram of a PDTF connected to a nonlinear load can be obtained. According to the superposition principle, an equivalent diagram of a PDTF connected to a NL is shown in Fig. 4.


그림입니다.
원본 그림의 이름: CLP00000f140005.bmp
원본 그림의 크기: 가로 811pixel, 세로 540pixel

Fig. 4. Equivalent diagram of a PDTF connected to an NL.


In Fig. 4, the power transformer is composed of a core, a primary winding, and a secondary winding. Among them, the power supply voltage is connected to the power supply winding N11; and the winding connections of the PDTF and NL are called the filter winding N12, and the non-linear load winding N13, respectively. N13 winding turns are equal to N12 winding turns. N11 can be regarded as the primary winding, and N12 and N13 can be regarded as the secondary windings.

The harmonic source in the winding N13 is replaced by the current source 그림입니다.
원본 그림의 이름: CLP00000f140006.bmp
원본 그림의 크기: 가로 64pixel, 세로 70pixel. Meanwhile the harmonic currents in the N11, N12 and N13 windings are 그림입니다.
원본 그림의 이름: CLP00000f140007.bmp
원본 그림의 크기: 가로 87pixel, 세로 80pixel, 그림입니다.
원본 그림의 이름: CLP00000f140008.bmp
원본 그림의 크기: 가로 90pixel, 세로 77pixel and 그림입니다.
원본 그림의 이름: CLP00000f140009.bmp
원본 그림의 크기: 가로 89pixel, 세로 70pixel, respectively. In addition, the harmonic current in the branch of the PDTF is 그림입니다.
원본 그림의 이름: CLP00000f14000a.bmp
원본 그림의 크기: 가로 60pixel, 세로 78pixel. Assuming that the equivalent harmonic impedance of the windings N11, N12 and N13 of the power transformer are ZT1h, ZT2h and ZT3h, the harmonic impedance of the PDTF is ZTf. An equivalent circuit can be obtained from Fig. 4, as shown in Fig. 5.


그림입니다.
원본 그림의 이름: image3.png
원본 그림의 크기: 가로 742pixel, 세로 502pixel

Fig. 5. Equivalent harmonic model of a power transformer and the PDTF connection.


The relationship between the equivalent harmonic current of winding N11 and winding N13 is:

그림입니다.
원본 그림의 이름: CLP00000f14000b.bmp
원본 그림의 크기: 가로 901pixel, 세로 186pixel        (3)

It can be seen from Equ. (3) that for the hth harmonic, as long as the harmonic current in winding N11 of the transformer is equal to zero, it is necessary for:

그림입니다.
원본 그림의 이름: CLP00000f14000c.bmp
원본 그림의 크기: 가로 343pixel, 세로 93pixel           (4)

The structure and parameters of the PDTF can be designed to satisfy Equ. (4). In this case, the harmonic current 그림입니다.
원본 그림의 이름: CLP00000f14000d.bmp
원본 그림의 크기: 가로 99pixel, 세로 90pixel can be zero in the ideal state. Therefore, the PDTF can completely suppress the harmonics generated by the NL.

The PDTF is designed according to the dynamic L-C parameters. This is the full-tuning method based on the fundamental equivalent impedance and the harmonic impedance.



IV. HARMONIC SUPPRESSION PRINCIPLE OF THE PDTF

The harmonics in a current waveform can be regarded as integer multiples at a certain fundamental frequency, e.g., 그림입니다.
원본 그림의 이름: CLP00000f14000e.bmp
원본 그림의 크기: 가로 200pixel, 세로 75pixel Hz. Thus, 그림입니다.
원본 그림의 이름: CLP00000f14000f.bmp
원본 그림의 크기: 가로 286pixel, 세로 77pixel, where h is the harmonic order.

Taking the harmonic current as an example, its expression is:

그림입니다.
원본 그림의 이름: CLP00000f140010.bmp
원본 그림의 크기: 가로 529pixel, 세로 190pixel             (5)

where 그림입니다.
원본 그림의 이름: CLP00000f140011.bmp
원본 그림의 크기: 가로 84pixel, 세로 91pixel denotes the peak value of the fundamental current and 그림입니다.
원본 그림의 이름: CLP00000f140012.bmp
원본 그림의 크기: 가로 80pixel, 세로 87pixel is the peak value of the hth harmonic current.

As can be known from Section II, for a propulsion inverter load with a 6-pulse rectifier circuit, the harmonic currents are of the 5th, 7th, 11th and 13th order. In other words, the values of h are 5, 7, 11 and 13. This shows that for the harmonics generated by a 6-pulse frequency converter, the 5th harmonic should be filtered first, followed by the 7th, 11th and 13th harmonics successively.

When the ECRITHS and the FCG are in series resonance in the PDTF, it is possible to obtain:

그림입니다.
원본 그림의 이름: CLP00000f140013.bmp
원본 그림의 크기: 가로 362pixel, 세로 161pixel              (6)

where ω1 represents the fundamental angular frequency of the power grid. When the capacitance of the filter capacitor Cs decreases due to dielectric aging or other reasons, the resonant point of the PDTF can be returned to the harmonic frequency by adjusting the equivalent inductance Ls.

Under normal conditions, the resonant frequency is fh (h=5, 7, 11 and 13), and the impedance of the filter branch is very small. When the capacitance of the filter capacitor Cs decreases, the resonant frequency fh of the PDTF increases to f. Meanwhile, the resonant point gradually shifts to a higher frequency when the service time of the capacitor increases.

The total impedance Zhf of the branch where the PDTF is located is:

그림입니다.
원본 그림의 이름: CLP00000f140014.bmp
원본 그림의 크기: 가로 854pixel, 세로 196pixel           (7)

When the reactor Ls and the capacitor Cs are in series resonance, the imaginary part in Equ. (7) is 0. Therefore:

그림입니다.
원본 그림의 이름: CLP00000f140015.bmp
원본 그림의 크기: 가로 700pixel, 세로 194pixel            (8)

where XL1 and XC1 denote the inductive reactance value and the capacitive reactance value of the ECRITHS at the fundamental angular frequency ω1 of the power grid.

The capacitance of the filter capacitor QC, the capacitance value Cs, the capacitance value XC and the resonance frequency fh are formulated as follows:

그림입니다.
원본 그림의 이름: CLP00000f140016.bmp
원본 그림의 크기: 가로 349pixel, 세로 315pixel             (9)

그림입니다.
원본 그림의 이름: CLP00000f140017.bmp
원본 그림의 크기: 가로 631pixel, 세로 184pixel          (10)

where XLh and XCh represent the inductive reactance value and the capacitive reactance value of the ECRITHS at the resonant frequency fh, respectively. If the capacity QC of the filter capacitor decreases, the capacitance reactance XC1 of the filter capacitor increases. However, Cs decreases, and the resonance frequency fh increases. Thus, the PDTF deviates from the original resonance point and the accuracy of the filter declines. At this point, if Ls is properly increased, the PDTF can return to the previous resonance point.

The PDTF can dynamically filter the harmonic current of the corresponding order at the resonant frequency. It can also overcome the detuning caused by the change of the capacitance parameter or other reasons.

Reactive power compensation of the PDTF under the fundamental wave is another key issue. According to the reactive power of the system, the capacity of the input capacitor can be flexibly changed to prevent the system from reactive power under-compensation and over-compensation.

The impedance Zf1 of the PDTF under the fundamental wave is:

그림입니다.
원본 그림의 이름: CLP00000f140018.bmp
원본 그림의 크기: 가로 1176pixel, 세로 177pixel       (11)

where XCs1 is the capacitance reactance value of the PDTF at the fundamental angular frequency.

According to Eqns. (9) and (10), the capacitive reactive power QP provided by the PDTF at the fundamental frequency is:

그림입니다.
원본 그림의 이름: CLP00000f140019.bmp
원본 그림의 크기: 가로 1041pixel, 세로 188pixel        (12)

where U1 denotes the fundamental voltages at both ends of the filter capacitor, and UCN and QCN are the rated voltage and capacity of the capacitor, respectively.



V. CHARACTERISTICS OF THE ECRITHS

The PEIC is regulated by the thyristor three-phase full- control mode. In the process of impedance transformation, a certain amount of 6k±1 (k=1, 2…) order harmonics is generated. For this reason, this paper invents an ECRITHS. The IF is designed to suppress the harmonics generated by the PEIC. Based on the structure of the ECRITHS, the mathematical equation of the harmonic influence coefficient is constructed. Using the MATLAB 2016b simulation tool, the harmonic suppression and the impedance transformation impedance transformation characteristics of the ECRITHS are simulated.


A. Structure of the ECRITHS

The ECRITHS is based on the electromagnetic coupling reactor (ECR) structure [10], with the secondary filtering winding N2 added, as shown in Fig. 6.


그림입니다.
원본 그림의 이름: CLP00000f14001a.bmp
원본 그림의 크기: 가로 1152pixel, 세로 754pixel

Fig. 6. Structure of the ECRITHS.


In Fig. 6, a single winding iron core reactor is designed as an electromagnetic coupling reactance converter (ECRC) with the primary reactance winding N1, the secondary filter winding N2 and the secondary control winding N3. N3 is connected to the PEIC, and N2 is connected to the IF, which forms a harmonic-free electromagnetic coupling reactor. The impedance transformation of the ECRITHS is realized by the PEIC, and the harmonic suppression of the ECRITHS is realized by the IF. A detailed graphic symbol description of the ECRITHS is given in Table II.


TABLE II DETAILED GRAPHIC SYMBOL DESCRIPTION OF THE ECRITHS

Graphic symbol

Description

N1(A, X)

Primary reactance winding of ECRC

N2(a2, x)

Secondary filter winding of ECRC

N3(a3, x)

Secondary control winding of ECRC

u1, u2, u3

Voltage of N1, N2, N3, respectively

i1, i2, i3

Current of N1, N2, N3, respectively

e1, e2, e3

Inductive potential of N1, N2, N3,  respectively

e1σ, e2σ, e3σ

Leakage potential of N1, N2, N3, respectively


B. Mathematical Equation of the Harmonic Influence Coefficient

In order to facilitate the mathematical model analysis of the ECRITHS, a simplified equivalent circuit of the ECRITHS can be obtained by simplifying the structure of Fig. 6, as shown in Fig. 7.


그림입니다.
원본 그림의 이름: image28.png
원본 그림의 크기: 가로 831pixel, 세로 563pixel

Fig. 7. Simplified equivalent circuit of the ECRITHS.


In Fig. 7, assuming that there is no harmonic component in the primary reactance winding of the ECRC, the harmonic generated by the PEIC is replaced by the current source 그림입니다.
원본 그림의 이름: CLP00000f14001b.bmp
원본 그림의 크기: 가로 54pixel, 세로 71pixel. In addition, the harmonic currents in the primary reactance winding N1 , the secondary filter winding N2 and the secondary control winding N3 are 그림입니다.
원본 그림의 이름: CLP00000f14001c.bmp
원본 그림의 크기: 가로 60pixel, 세로 69pixel, 그림입니다.
원본 그림의 이름: CLP00000f14001d.bmp
원본 그림의 크기: 가로 65pixel, 세로 66pixel and 그림입니다.
원본 그림의 이름: CLP00000f14001e.bmp
원본 그림의 크기: 가로 67pixel, 세로 65pixel. The harmonic currentsabsorbed by the IF is 그림입니다.
원본 그림의 이름: CLP00000f14001f.bmp
원본 그림의 크기: 가로 59pixel, 세로 79pixel. The equivalent harmonic impedance of N1, N2, N3 and IF are Z1h, Z2h, Z3h and Zf, respectively.

As shown in Fig. 7, the relationship between the hth subharmonic current and the voltage is:

그림입니다.
원본 그림의 이름: CLP00000f140020.bmp
원본 그림의 크기: 가로 254pixel, 세로 186pixel                   (13)

그림입니다.
원본 그림의 이름: CLP00000f140021.bmp
원본 그림의 크기: 가로 408pixel, 세로 189pixel            (14)

The harmonic current and voltage of N1 and N2 are converted as follows:

그림입니다.
원본 그림의 이름: CLP00000f140022.bmp
원본 그림의 크기: 가로 514pixel, 세로 613pixel             (15)

Without taking the excitation current into consideration, the equivalent harmonic circuit corresponding to Fig. 7 is obtained, as shown in Fig. 8.


그림입니다.
원본 그림의 이름: image29.PNG
원본 그림의 크기: 가로 1403pixel, 세로 669pixel

Fig. 8. Equivalent harmonic circuit of the ECRITHS.


From Fig. 8, the equivalent harmonic impedance relation of the ECRITHS can be obtained as follows:

그림입니다.
원본 그림의 이름: CLP00000f140027.bmp
원본 그림의 크기: 가로 741pixel, 세로 514pixel         (16)

where the harmonic equivalent impedance relationships of the ECRITHS are shown in Table III.


TABLE III HARMONIC EQUIVALENT IMPEDANCE RELATIONSHIP OF THE ECRITHS

Serial Number

Position

Harmonic equivalent impedance

Turn ratio relationship

1

N1 and N2

그림입니다.
원본 그림의 이름: CLP00000f140024.bmp
원본 그림의 크기: 가로 406pixel, 세로 84pixel

Reciprocal

2

N1 and N3

그림입니다.
원본 그림의 이름: CLP00000f140025.bmp
원본 그림의 크기: 가로 234pixel, 세로 69pixel

Reciprocal

3

N2 and N3

그림입니다.
원본 그림의 이름: CLP00000f140026.bmp
원본 그림의 크기: 가로 425pixel, 세로 92pixel

Reciprocal


According to the KCL equation of the node, the equation of the zine potential of the hth harmonic current can be obtained as:

그림입니다.
원본 그림의 이름: CLP00000f140028.bmp
원본 그림의 크기: 가로 398pixel, 세로 87pixel             (17)

Using the superposition principle, the following voltage equation is obtained from Fig. 8:

그림입니다.
원본 그림의 이름: CLP00000f140029.bmp
원본 그림의 크기: 가로 833pixel, 세로 214pixel         (18)

Substituting Eqns. (13)-(15) into Equ. (18) yields:

그림입니다.
원본 그림의 이름: CLP00000f14002a.bmp
원본 그림의 크기: 가로 985pixel, 세로 325pixel      (19)

Simplifying Equ. (19) yields:

그림입니다.
원본 그림의 이름: CLP00000f14002b.bmp
원본 그림의 크기: 가로 1207pixel, 세로 156pixel      (20)

From Equ. (20):

그림입니다.
원본 그림의 이름: CLP00000f14002c.bmp
원본 그림의 크기: 가로 700pixel, 세로 292pixel            (21)

Substituting Equ. (16) into Equ. (21) yields:

그림입니다.
원본 그림의 이름: CLP00000f14002d.bmp
원본 그림의 크기: 가로 995pixel, 세로 325pixel         (22)

The harmonic equivalent impedance relationship of the electromagnetically coupling reactor shown in Table III is substituted into Equ. (22) and simplified:

그림입니다.
원본 그림의 이름: CLP00000f14002e.bmp
원본 그림의 크기: 가로 525pixel, 세로 182pixel              (23)

Substituting Eqns. (15) and (23) into Equ. (21), and simplifying them yields the harmonic influence coefficient Kh:

그림입니다.
원본 그림의 이름: CLP00000f14002f.bmp
원본 그림의 크기: 가로 882pixel, 세로 195pixel        (24)

Equ. (24) reveals the relationship between the equivalent harmonic currents of N1 and N3. The harmonic influence of the harmonic source generated by the PEIC on N3 is related to Kh, as in the following.

(1) When Kh=0, Z2h+Zf=0 and I1h=0, it is indicated that the IF has the best harmonic suppression effect.

(2) When 0<Kh<1: the smaller the value of Kh, the smaller the influence. On the other hand, the larger the value of Kh, the greater the influence.

(3) When Kh=1 and I1h=Ih, the influence is the greatest.

Therefore, it can be concluded that as long as the sum of the harmonic impedance Z2h of N2 and the impedance Zf of the IF is zero, the IF can completely suppress the harmonic current generated by the PEIC.


C. Simulation of the Harmonic Suppression Characteristics of the ECRITHS

A simulation model of the harmonic suppression characteristics of the ECRITHS is constructed according to Eq. (24), as shown in Fig. 9.


그림입니다.
원본 그림의 이름: image44.png
원본 그림의 크기: 가로 685pixel, 세로 376pixel

Fig. 9. Simulation model of the harmonic suppression characteristics of the ECRITHS.


Taking the filtering of the 5th harmonic current as the research object, an LfCf passive filter is used in the IF, where the capacitor selected is 10 kVar, and the capacitor voltage is 525V. The harmonic suppression characteristics of the ECRITHS are simulated and analyzed, including a relationship curve between the harmonic influence coefficient Kh and the IF impedance Zf, as shown in Fig.10.


그림입니다.
원본 그림의 이름: CLP00000f140033.bmp
원본 그림의 크기: 가로 1236pixel, 세로 596pixel

Fig. 10. Relation curve between the harmonic influence coefficient 그림입니다.
원본 그림의 이름: CLP00000f140030.bmp
원본 그림의 크기: 가로 76pixel, 세로 73pixel and the IF impedance 그림입니다.
원본 그림의 이름: CLP00000f140031.bmp
원본 그림의 크기: 가로 80pixel, 세로 84pixel.


From Fig. 10, the validity of formula (24) is verified. The influence of the harmonic source produced by N3 on the harmonic of N1 is related to Kh. The harmonic influence coefficient Kh decreases linearly with the increase of Zf, with its slope determined by the parameters of the ECRITHS. Therefore, it can be concluded that the harmonic current generated by N3 can be completely absorbed by the IF, if Zf can be adjusted to make 그림입니다.
원본 그림의 이름: CLP00000f140038.bmp
원본 그림의 크기: 가로 77pixel, 세로 74pixel close to 0.


D. Simulation of the Impedance Transformation Characteristics of the ECRITHS at the Fundamental Frequency

Firstly, an impedance transformation simulation model of the ECRITHS is constructed according to the impedance transformation mathematical model of the ECRITHS. Then an impedance transformation characteristic curve of the ECRITHS is obtained by simulation.

When the PEIC operates between the “open state and the short circuit state” with the excitation current (Zm=∞) being ignored, the impedance transformation mathematical model of the ECRITHS [10] is as follows:

그림입니다.
원본 그림의 이름: CLP00000f14003a.bmp
원본 그림의 크기: 가로 1146pixel, 세로 297pixel       (25)

An impedance transformation simulation model of the ECRITHS is constructed according to Equ. (25). According to the simulation of design parameters of the ECRITHS in Table IV, an impedance transformation characteristic curve of the ECRITHS at the fundamental frequency is obtained, as shown in Fig. 11.


TABLE IV DESIGN PARAMETERS OF THE ECRITHS

Basic parameters

Number of turns

1: 5

capacity /kVA

5

Primary reactance winding N1

N1

40

Current I1/A

75

Voltage U1/V

38

Inductance 그림입니다.
원본 그림의 이름: CLP00000f140034.bmp
원본 그림의 크기: 가로 73pixel, 세로 88pixel/mH

1.62

Resistance 그림입니다.
원본 그림의 이름: CLP00000f140035.bmp
원본 그림의 크기: 가로 71pixel, 세로 92pixel/Ω

0.0324

Secondary harmonic winding N2

N2

200

 

Current I2/A

15

 

Voltage U2/V

190

 

Inductance 그림입니다.
원본 그림의 이름: CLP00000f140036.bmp
원본 그림의 크기: 가로 72pixel, 세로 85pixel/mH

1.852

 

Resistance 그림입니다.
원본 그림의 이름: CLP00000f140037.bmp
원본 그림의 크기: 가로 78pixel, 세로 87pixel/Ω

0.0369

 

Secondary control winding N3

N3

200

 

Current I3/A

15

 

Voltage U3/V

190

 

Inductance L3/mH

1.852

 

Resistance R3/Ω

0.0369

 


그림입니다.
원본 그림의 이름: CLP00000f140039.bmp
원본 그림의 크기: 가로 1434pixel, 세로 683pixel

Fig. 11. Impedance transformation characteristic curve of the ECRITHS.


The following conclusions can be verified from Fig. 11. The ECRITHS is equivalent to a reactor with a variable inductance. The impedance conversion characteristics of the ECRITHS are shown in Table V.


TABLE V IMPEDANCE CONVERSION CHARACTERISTICS OF THE ECRITHS

π-α/

Z11/Ω

Characteristics description

0

Maximum 

N3 of ECRC is short-circuited

0∼10

Rapid decrease

Z11minZ11Z11max

10∼30

Change significantly

30∼120

Change slowly

120

Minimum 

N3 of ECRC is open-circuited



VI. SIMULATION AND EXPERIMENTAL EVALUATION OF THE PDTF


A. Simulation evaluation of the PDTF

Numerical simulations have been conducted to validate the PDTF used for the harmonic suppression of a ship electric propulsion system. A simulation model for the harmonic suppression of a ship electric propulsion system is constructed according to the above research results, as shown in Fig. 12.


Fig. 12. Simulation model for the harmonic suppression of a ship electric propulsion system. (a) Simulation model. (b) Simulink schematic of a field-oriented control induction motor drive (FOCIMD).

그림입니다.
원본 그림의 이름: image57.png
원본 그림의 크기: 가로 658pixel, 세로 516pixel

(a)

 

그림입니다.
원본 그림의 이름: image58.png
원본 그림의 크기: 가로 722pixel, 세로 395pixel

(b)


In Fig. 12, the implement three-phase source is selected as the Power Supply (PS), with speed and load torque set by the SV module. Signals are saved and scoped by the SS module. The harmonics are produced by two FOCIMDs, which are used to drive propellers 1 and 2 (see in Fig. 2). The three- phase inverter in Fig. 12(b) is the propulsion inverter with a 6-pulse rectifier circuit. Therefore, the PDTF consisting of four PDTFs (5th, 7th, 11th and 13th) are connected in parallel with the two harmonic sources (FOCIMD 1 and 2). Four PDTFs have been applied to eliminating the harmonics of a ship power system with the proposed method for dynamic tuning of the PDTF in the above simulation system.

According to the simulation parameters of the induction motor in Table VI, the speed reference is set to 1000rpn, and load torque is set to 792NM. Using a Powergui FFT Analysis Tool, simulated results of the 5th, 7th, 11th and 13th harmonic currents and the THD in the source current (VI0) with and without the PDTF are shown in Table VII. In addition, current curves in the VI0 with and without the PDTF are shown in Fig. 13.


TABLE VI SIMULATION PARAMETERS OF THE INDUCTION MOTOR

Electrical Parameters

Power/kVA

149.2

Voltage/V

460

Frequency/Hz

50

Equivalent circuit values

Resistance/Ω(Stator)

14.85×10-3

Leakage inductance/mH (Stator)

0.3027

Resistance/Ω(Rotor)

9.295×10-3

Leakage inductance/mH (Roator)

0.3027

Mutual inductance/mH

10.46

Mechanical Parameters

Inertia/kg*m2

3.1

Friction

0.08

Pole Pairs

2


TABLE VII SIMULATED RESULTS OF HARMONIC SUPPRESSION

Harmonic order

Cs/uF

Ls/mH

Harmonic Current /A

without PDTF

With PDTF

Absorption

5th

1501.5

0.270

138.11

19.31

118.8

7th

693

0.298

75.98

17.46

58.52

11th

288.75

0.290

14.46

9.43

5.03

13th

115.5

0.519

15.60

8.79

6.81

THD /%

-

 

67.34

4.64

-


Fig. 13. Current curve in the VI0. (a) Without the PDTF. (b) With the PDTF.

그림입니다.
원본 그림의 이름: CLP00000f14003b.bmp
원본 그림의 크기: 가로 1233pixel, 세로 518pixel

(a)

 

그림입니다.
원본 그림의 이름: CLP00000f14003c.bmp
원본 그림의 크기: 가로 1241pixel, 세로 510pixel

(b)


As can be seen, the current is0 (Fig. 13(a)) in the VI0 without the PDTF contains a significant number of harmonics, and the current is1 (Fig. 13(b)) in the source current with the PDTF contains a lot fewer harmonics than is0. The magnitudes of the harmonic spectrum are shown in Fig. 14.

Fig. 14. Magnitudes of the harmonic spectrum in the VI0. (a) Without the PDTF. (b) With the PDTF.

그림입니다.
원본 그림의 이름: CLP00000f14003d.bmp
원본 그림의 크기: 가로 1222pixel, 세로 515pixel

(a)

 

그림입니다.
원본 그림의 이름: CLP00000f14003e.bmp
원본 그림의 크기: 가로 1242pixel, 세로 515pixel

(b)



The following conclusions can be verified from Table VII, Fig. 13 and Fig. 14. The THD of the source current is 67.34%, which is reduced to about 4.64% by the multi-order simultaneous dynamic filtering. At the same time, the harmonic current can be absorbed by the PDTF, with the absorption efficiency rate of the 5th harmonic current being above 80%. It has been found that multiple PDTFs can be configured to realize multi- order simultaneous dynamic filtering, and can reduce the THD of source currents well below the 5% limit of the IEEE-519 standard [11].


B. Experimental Evaluation of the PDTF

Pictures of the PDTF are shown in Fig. 15, and it has been applied to eliminate the harmonics of a low voltage distribution system, with a transformer capacity of 1250kVA and a ratio of 6.3kV/0.4kV. There are five harmonic sources (HS1- HS5) in different geographic places. The harmonics are produced by five variable-frequency drives (VFD1-VFD5), which are used to drive the motors (M1-M5), respectively. A configuration diagram of the main electric cabinet is shown in Fig. 16.


그림입니다.
원본 그림의 이름: CLP00000f14003f.bmp
원본 그림의 크기: 가로 989pixel, 세로 758pixel

Fig. 15. Pictures of the PDTF.


그림입니다.
원본 그림의 이름: CLP00000f140040.bmp
원본 그림의 크기: 가로 1121pixel, 세로 898pixel

Fig. 16. Schematic diagram of the main electrical configuration in a distribution system.


The 5th harmonic current (I5), THD, fundamental current (I1) in the HC0 and TP1~ TP5 are measured using a power quality analyzer (CA8335), where the measurement results of the distribution system are shown in Table VIII.


TABLE VIII MEASUREMENT RESULTS OF THE DISTRIBUTION SYSTEM WITHOUT THE PDTF

Test point

Rated Power/kW

I1/A

I5/A

THD/%

HC0

-

1365

97

7.2

HC1

75

93.2

29.6

31.7

HC2

75

72.4

26.6

41.2

HC3

75

96.6

30.4

32.8

HC4

75

102.2

30.4

32

HC5

50

86

25.4

29


Five PDTFs are connected in parallel with five harmonic sources (HS1- HS5) (See Fig. 16 for details). Graphs of the 5th harmonic current (I5) and its total harmonic distortion (THD) in the HC0 are shown in Fig. 17.


Fig. 17. Graphs of I5 and THD in the HC0. (a) I5 and THD before filtering. (b) I5 and THD with the PDTF. (c) I5 and THD with a PPF.

그림입니다.
원본 그림의 이름: CLP00000f140043.bmp
원본 그림의 크기: 가로 718pixel, 세로 472pixel

(a)

그림입니다.
원본 그림의 이름: CLP00000f140041.bmp
원본 그림의 크기: 가로 744pixel, 세로 483pixel

(b)

그림입니다.
원본 그림의 이름: CLP00000f140042.bmp
원본 그림의 크기: 가로 745pixel, 세로 480pixel

(c)


Filtering performances of the PDTF and a PPF as shown in Fig.17 (taking phase A as an example) are as follows.

(1) Before filtering (Fig. 17(a)), the 5th harmonic current and the THD of the nonlinear load are 97A and 7.2%, respectively.

(2) With the dynamic filtering method (PDTF) proposed in this paper (Fig. 17(b)), the 5th harmonic current and the THD are reduced to 46A and 3.6%, respectively. The PDTF absorbed 51A of the 5th harmonic current. The absorption rate is 52.6%. The THD decreased by 50%.

(3) By the traditional passive filtering method (PPF), the 5th harmonic current and current distortion rate are 66.6A and 5.3%, respectively. The PPF absorbed 30.4A of the 5th harmonic current. The absorption rate is 33.4%. The THD decreased by 26.3%.

It can be seen from the above results that, under the same nonlinear load, the dynamic filtering method proposed in this paper is superior to the traditional passive filtering method and that its filtering performance is excellent.

The PDTF has been proposed to eliminate harmonic currents at different geographic places to comply with the IEEE-519 harmonic standard [11] by using a low voltage distribution system. It has been found that the PDTF can effectively eliminate current harmonics in different geographic places. It has been shown that the PDTF is able to reduce the THD of supply currents to well below the 5% limit prescribed by the IEEE-519 standard.



VII. CONCLUSIONS

According to the harmonic characteristics of a ship electric propulsion system, their treatment methods and effective measurements have been studied to suppress and prevent the ship power system from affecting ship operation due to the serious damage caused by harmonics. By analyzing the PDTF, the control principle is discussed in detail. In addition, a method for fully tuning of the PDTF is proposed. Through the structure design of the ECRITHS and harmonic influence coefficient modeling, simulation evaluations are completed. The ECRITHS is equivalent to a reactor with a variable inductance. The designed IF can suppress the harmonics generated by the PEIC. It can be concluded that the harmonic current generated by the PEIC can be completely absorbed by the IF, if 그림입니다.
원본 그림의 이름: CLP00000f140044.bmp
원본 그림의 크기: 가로 69pixel, 세로 65pixel can be adjusted close to 0. Experiments on the harmonic suppression of a ship electric power propulsion system have been completed. Multiple PDTFs can be configured to realize multi-order simultaneous dynamic filtering, and can effectively eliminate the current harmonics of the ship electric propulsion system to reduce the THD of the supply currents to well below the 5% limit prescribed by the IEEE-519 standard [11]. The PDTFs can also eliminate harmonic currents in different geographic places. It has been shown that the PDTF is able to reduce the THD of supply currents to well below the 5% limit specified by the IEEE-519 standard.

It is believed that this research is promising when a sufficiently developed technological basis is available. In order to further eliminate the detuning caused by filter capacitor capacity variation, an analysis and discussion should be made on the influence of the harmonic suppression of different filter capacitors on ship electric propulsion systems in future studies.



ACKNOWLEDGMENT

This work was supported by the National Support Program of China (#2015BAG20B05), the Zhejiang Province Natural Science Foundation of China (#LY14E070003), and the Independent Innovation Fund Project of Wuhan University of Technology (#2018-JL-004).



REFERENCES

[1] Y. Zhang, P. X. Yang, and L. Chen, “Harmonic characteristic research of the synchronous generator propulsion converter system in electric propulsion,” Ship Eng., Vol. 31, No. z1, pp. 98-101, Jul. 2009.

[2] D. R. Zhang, “Design and simulation of harmonic suppressor for multiphase rectifier in marine electric propulsion system,” Ship Sci. Technol., Vol. 38, No. 12A, pp. 43-45, Dec. 2016.

[3] X. Xu and Q. Shi, “Power quality improvement method in marine electric propulsion system,” Electr. Eng., No. 8, pp. 54-57, Aug. 2010.

[4] J. S. Kim and S. H. Kim, “Harmonic analysis of power conversion system for torque and speed changing of electric propulsion ship,” J. Korean Soc. Mar. Environ. Saf., Vol. 17, No. 1, pp. 83-88, Mar. 2011.

[5] P. Xiao, G. K. Venayagamoorthy, and K. A. Corzine, “Seven-level shunt active power filter for high-power drive systems,” IEEE Trans. Power Electron., Vol. 24, No. 1, pp. 6-13, Jan. 2009.

[6] D. Li, K. Yang, Z. Q. Zhu, and Y. Qin, “A novel series power quality controller with reduced passive power filter,” IEEE Trans. Ind. Electron., Vol. 64, No. 1, pp. 773-784, Jan. 2017.

[7] R. N. Beres, X. Wang, M. Liserre, F. Blaabjerg, and C. L. Bak, “A review of passive power filters for three-phase grid-connected voltage-source converters,” IEEE J. Emerg. Sel. Topics Power Electron., Vol. 4, No. 1, pp. 54-69, Mar. 2016.

[8] Y. Wang, Y. Yuan, J. Chen, and Q. Cheng, “A dynamic reactive power compensation method of super high-power and high-voltage motor,” Appl. Mech. Mater., Vols. 602-605, pp. 2828-2831, Aug. 2014.

[9] E. Skjong, J. A. Suul, A. Rygg, T. A. Johansen, and M. Molinas, “System-wide harmonic mitigation in a diesel electric ship by model predictive control,” IEEE Trans. Ind. Electron., Vol. 63, No. 7, pp. 4008-4019, Jul. 2016.

[10] Y. Wang, Y. Yuan, and J. Chen, “A novel electromagnetic coupling reactor based passive power filter with dynamic tunable function,” Energies, Vol. 11, No. 7, pp. 1647-1665, Jun. 2018.

[11] P. E. C. Stone, J. Wang, R. Dougal, and Y. J. Shin, “Strategic harmonic filter placement in an electric ship integrated power system,” Nav. Eng. J., Vol. 128, No. 1, pp. 35-46, Mar. 2016.

[12] O. F. Kececioglu, H. Acikgoz, and M. Sekkeli, “Advanced configuration of hybrid passive filter for reactive power and harmonic compensation,” Springer Plus, Vol. 5, No. 1, pp. 1228-1247, Aug. 2016.

[13] S. H. E. A. Aleem, M. E. Balci, and S. Sakar, “Effective utilization of cables and transformers using passive filters for non-linear loads,” Int. J. Electr. Power Energy Syst., Vol. 71, pp. 344-350, Oct. 2015.

[14] A. M. Othman and H. A. Gabbar, “Enhanced microgrid dynamic performance using a modulated power filter based on enhanced bacterial foraging optimization,” Energies, Vol. 10, No. 6, pp. 776-788, Jun. 2017.

[15] M. Mohammadi, A. M. Rozbahani, and M. Montazeri, “Multi criteria simultaneous planning of passive filters and distributed generation simultaneously in distribution system considering nonlinear loads with adaptive bacterial foraging optimization approach,” Int. J. Electr. Power Energy Syst., Vol. 79, pp. 253-262, Jul. 2016.

[16] S. P. Litran and P. Salmeron, “Analysis and design of different control strategies of hybrid active power filter based on the state model,” IET Power Electron., Vol. 5, No. 8, pp. 1341-1350, Sep. 2012.

[17] M. Kale and E. Ozdemir, “An adaptive hysteresis band current controller for shunt active power filter,” Electr. Power Syst. Res., Vol. 73, No. 2, pp. 113-119, Feb. 2005.

[18] J. Fang, H. Li, and Y. Tang, “A magnetic integrated LLCL filter for grid-connected voltage-source converters,” IEEE Trans. Power Electron., Vol. 32, No. 3, pp. 1725-1730, Mar. 2017.

[19] J. C. Leite, I. P. Abril, M. E. D. L. Tostes, and R. C. L. D. Oliveira, “Multi-objective optimization of passive filters in industrial power systems,” Electr. Eng., Vol. 99, No. 1, pp. 387-395, Mar. 2017.

[20] V. S. R. V. Oruganti, A. S. Bubshait, V. S. S. S. S. Dhanikonda, and M. G. Simoes, “Real-time control of hybrid active power filter using conservative power theory in industrial power system,” IET Power Electron., Vol. 10, No. 2, pp. 196-207, Feb. 2017.

[21] T. Ericsen, N. Hingorani, and Y. Khersonsky, “Power electronics and future marine electrical systems,” IEEE Trans. Ind. Appl., Vol. 42, No. 1, pp. 155-163, Jan. 2006.

[22] N. He, D. Xu, and L. Huang, “The application of particle swarm optimization to passive and hybrid active power filter design,” IEEE Trans. Ind. Electron., Vol. 56, No. 8, pp. 2841-2851, Aug. 2009.

[23] Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, “Generalized design of high performance shunt active power filter with output LCL filter,” IEEE Trans. Ind. Electron., Vol. 59, No. 3, pp. 1443-1452, Mar. 2012.

[24] H. H. Zeineldin and A. F. Zobaa, “Particle swarm optimization of passive filters for industrial plants in distribution networks,” Electr. Power Compon. Syst., Vol. 39, No. 16, pp. 1795-1808, Oct. 2011.

[25] Y. Wang and Y. Yuan, “Development of a soft starter with current-limiting, reactive power compensation and harmonic filtering,” Appl. Mech. Mater., Vols. 462-463, pp. 658-661, Nov. 2013.

[26] Y. Wang, Y. Yuan, Y. Chang, and Y. Xu, “A novel soft starting integration method with current-limiting, reactive power compensation for super high-power and high-voltage motor and harmonic filtering,” J. Wuhan. Univ. Technol., Vol. 35, No. 7, pp. 140-143, Jul. 2013.

[27] Y. Wang and Y. Yuan, “A dynamic reactive power compensation method for high-power and high-voltage electronic motors based on self-adaptive fuzzy pid control,” in Proceedings of the 2016 IEEE Chinese Guidance, Navigation and Control Conference, pp. 10-15, 2016.

[28] J. Chen, L. Xiao, Y. Yuan, K. Yang, L. Lei, B. Mao, and Z. Chen, “Development of Passive dynamic power filter based on MCU,” J. Wuhan. Univ. Technol., Vol. 35, No. 2, pp. 144-146, Feb. 2013.

[29] J. Li, J. Chen, Y. Deng, and J. Li, “Modeling and simulation of passive dynamic harmonic filter based on IGBT,” Appl. Mech. Mater., Vols. 475-476, pp. 1615-1618, Dec. 2013.



그림입니다.
원본 그림의 이름: image84.jpeg
원본 그림의 크기: 가로 98pixel, 세로 116pixel

Yifei Wang was born in Chongqing, China, in 1990. He received his M.S. degree in Control Science and Engineering from the Wuhan University of Technology, Wuhan, China, in 2013, where he is presently working towards his Ph.D. degree. In 2017, he was invited to spend two years conducting joint training as a Visiting Ph.D. Student at the University of Wisconsin-Madison, Madison, WI, USA. His current research interests include power electronic, computer control and harmonic suppression.


그림입니다.
원본 그림의 이름: image85.png
원본 그림의 크기: 가로 190pixel, 세로 225pixel

Youxin Yuan was born in Hubei, China, in 1953. In 1977, he became an Assistant Teacher in the Department of Automation, Wuhan University of Technology, Wuhan, China, where he became an Associate Professor in 1991, and where he has been a Professor and Doctoral Supervisor since 2001 and 2006, respectively. His current research interests include power electronics, reactive power compensation and harmonic suppression.


그림입니다.
원본 그림의 이름: image86.jpeg
원본 그림의 크기: 가로 190pixel, 세로 225pixel

Jing Chen was born in Chongqing, China, in 1965. She received her M.S. and Ph.D. degrees from the Wuhan University of Technology, Wuhan, China, in 1997 and 2003, respectively. She is presently working as a Full Professor in the School of Automation, Wuhan University of Technology, Wuhan, China, where she has been a Professor and Doctoral Supervisor since 2004 and 2008, respectively. Her current research interests include control science and engineering, computer control, reactive power compensation and harmonic suppression.